Sealey AirPower SAC5020E.V3 Manual Download Page 3

5.  tool selectioN

 

‰

   importANt 

Take care when selecting tools for use with the compressor. Air tool manufacturers normally express the volume of   

 

air required to operate a tool in cubic feet per minute (cfm). This refers to free air delivered by the compressor (‘air out’) which varies

  

  according to the pressure setting. 

do Not

 confuse this with the compressor displacement which is the air taken in by the compressor  

 

(‘air in’). ‘Air out’ is always less than ‘air in’ - due to losses within the compressor - and so it is important that, before choosing equipment, 

 

 

you study the ‘Free Air Delivery’ figures shown in the Specification Chart. 

6.  operAtioN

 

‰

   WArNiNG!

 

eNsUre thAt YoU hAve reAd, UNderstood ANd Applied sectioN 1 sAFetY iNstrUctioNs.

6.1. 

  

Make sure that the main switch (fig.3.1) is ‘OFF’ (down).

6.2. 

  

Check the oil level by looking through the sight glass (See fig.2B).

6.3. 

  

ensure that the tank drain valve is closed (fig.5).

6.4. 

  

Close the outlet pressure regulator by turning the knob clockwise (fig.3.2).

6.5. 

  

Connect the air tool required to the compressor via an air line connected to the air outlet. 

6.6. 

  

Plug the mains cable into the mains supply and start the compressor by pulling up the main switch.

6.7. 

  

Allow the pressure in the tank to rise to the maximum at which point the compressor will automatically cut out. Tank pressure is shown on  

 

the larger gauge (fig.3.5).

6.8. 

  

Begin to gradually open the regulator by turning the knob until the small gauge registers the required operating pressure specified for the  

 

tool to be used. Always 

adjust up

 to the required pressure rather than down from a higher pressure. The required setting, once achieved,  

 

can be locked by screwing the locking ring (fig.3.3) up tight underneath the adjusting knob.

6.9. 

  

You can now begin to use the tool. The compressor will operate automatically cutting in and out as required to restore the air pressure  

 

in the tank. The pressure switch (fig.3.7) stops the motor when the maximum tank pressure is reached and restarts it when pressure falls  

 

below the minimum threshold - approximately 2bar (29psi) less than the maximum pressure.

  

Note: 

  a) 

If the motor does not cut in and out, but runs continuously when using an air appliance, the capacity of the   

 

  

 

compressor may be too small for the appliance.

 

  

b) 

The main gauge (fig.3.5) indicates the pressure inside the main tank, 

Not

 the pressure supplied to the air   

 

  

 

equipment, which is shown on the smaller gauge (fig.3.4). Should the pressure in the main tank exceed the pre-set  

 

  

 

switch (fig.3.7) maximum, the safety valve (fig.3.6) will activate. 

 

‰

  

WArNiNG! 

For this reason 

do Not

 tamper with, or adjust, the switch or the safety valve. 

 

When the compressor is not being used set the regulated pressure to zero so as to avoid damaging the pressure regulator. 

6.10. 

T

o stop the compressor press down the main switch (fig.3.1). When the compressor stops there will be a whistling sound as compressed 

 

 

air is vented from the compressor head. 

 

8

   do Not

, other than in an emergency, stop the compressor by switching off the mains power, or by pulling the plug out, as the pressure  

  relief will not then occur and motor damage may result upon restart. 

6.11. 

W

hen you have finished using the compressor unplug the unit from the mains power supply.

6.12. 

S

et the outlet pressure on the regulator to zero.

6.13. 

Remove the air line and air tool.

6.14. 

The tank must now be drained. This will release the air left in the tank and drain away condensation that may have formed within the tank.  

 

Choose a suitable location for this operation and/or make provision to collect the condensation. 

Wear ear and eye protection.

 open  

 

the tank drain valve (See fig.5) slowly allowing air and moisture to bleed from the tank. After bleeding close the drain valve to prevent  

 

debris building up in the valve.

 

‰

   WArNiNG!

 Water that is allowed to remain in the tank during storage will corrode and weaken the air tank which could cause the tank to  

  rupture. To avoid serious injury drain the tank after each use or daily. 

6.15. 

sAFetY FeAtUres 

6.15.1. 

Thermal cut out: If the unit overheats the thermal cut out will operate and shut the unit down. Allow the unit to cool down then press the  

 

reset button, located just inside the pump cover (fig.7). 

Original Language Version

© Jack Sealey limited

fig.3

fig.5

fig.4

S

AC5020E.V3, SAC5020EPK.V2   Issue 1    13/06/19

Summary of Contents for AirPower SAC5020E.V3

Page 1: ... the restraint is tight Sealey recommend that repairs are carried out by a qualified electrician 1 1 5 Products which require more than 13 amps are supplied without a plug Contact a qualified electrician to ensure that a suitably rated supply is available Ensure that an industrial round pin plug and socket are fitted by a qualified electrician 1 1 6 If an extension cable reel is used ensure that i...

Page 2: ...responsibility of the owner of the compressor to initiate a system of inspection that both defines the frequency of the inspection and appoints a person who has specific responsibility for carrying out the inspection 2 i introduction Aluminium cylinder head with cast iron cylinder gives added resistance to wear Suitable for general purpose workshop applications Pump head directly coupled to heavy ...

Page 3: ...bar 29psi less than the maximum pressure NOTE a If the motor does not cut in and out but runs continuously when using an air appliance the capacity of the compressor may be too small for the appliance b The main gauge fig 3 5 indicates the pressure inside the main tank NOT the pressure supplied to the air equipment which is shown on the smaller gauge fig 3 4 Should the pressure in the main tank ex...

Page 4: ...ll 7 4 2 Replace oil filler breather fig 2 7 5 RECOMMENDED OIL 7 5 1 Suitable for room temperatures ranging from 5ºC to 25ºC SEALEY CPO or equivalent SAE 40 compressor oil 7 5 2 Room temperature below 5ºC SAE 20 compressor oil WARNING Never mix different oils and DO NOT use non detergent low quality oils as the compressor may be damaged 7 5 3 Dispose of waste oil only in accordance with local auth...

Page 5: ...free from unrelated materials and ensure there is adequate lighting 9 9 Keep children and unauthorised persons away from the work area 8 8 DO NOT direct gauge outlet at yourself or at other persons or animals 8 8 DO NOT carry by the hose or yank the hose from the air supply 8 8 DO NOT use the gauge for a task which it is not designed to perform 8 8 DO NOT operate the gauge when you are tired or un...

Page 6: ...in the off position before connecting to the air supply WARNING Ensure the air supply is clean and does not exceed specification above while operating the tool Too high an air pressure and or unclean air will shorten the product life due to excessive wear and may be dangerous causing damage and or personal injury 14 1 2 Drain the air tank daily Water in the air line will ruin the paint finish and ...

Page 7: ... maintenance 16 1 Cleaning the gun 16 1 1 Flush the gun through with clean solvent 16 1 2 Use a bristle brush and solvent to wash off accumulated paint 16 1 3 Clean the air nozzle using a brush Blow clean with air Handle all nozzles carefully and do not make any alterations in the gun 16 1 4 Wipe the outside of the gun with a dampened solvent rag 16 1 5 If there is a need to probe the holes in the...

Reviews: