950-0203-revK - 21 - March 1, 2016
To adjust the differential (temperature between ON and OFF):
STEP1: Turn the temperature from
℉
to
℃
on the remote by press the "mode" and "-" button with the remote in
the OFF position.
STEP2: Within 30 seconds after the indoor unit is on the differential can be changed as below:
Alternately p
ress the “+” then “-“ button on the remote three times within 5 seconds while in the heating mode
with set point set to 17
℃
. The indoor unit will reset the temperature and deliver 3
℃
(5.4°F differential) signal to
the outdoor unit. At this time, 3
℃
will display on the indoor unit, LED of heating and operation would flash for
three times.
Alternately p
ress the “+” then “-“ button on remote three times within 5 seconds while in the heating mode with
set point set to 18
℃
. The indoor unit will reset the temperature and deliver 2
℃
(3.6°F differential) signal to the
outdoor unit. At this time, 2
℃
will display on the indoor unit, LED of heating and operation would flash for three
times.
Alternately p
ress the “+” then “-“ button on remote three times within 5 seconds while in the heating mode with
set point set to 19
℃
. The indoor unit will reset the temperature and deliver 1
℃
(1.8°F differential) signal to the
outdoor unit. At this time, 1
℃
will display on the indoor unit, LED of heating and operation would flash for three
times.
Alternately p
ress the “+” then “-“ button on remote three times within 5 seconds while in the heating mode with
set point 20
℃
. The indoor unit will reset the temperature and deliver 0
℃
(0°F differential) signal to the outdoor
unit. At this time, 0
℃
will display on the indoor unit, LED of heating and operation would flash for three times.
This selection is not recommended.
The compressor delay will be activated when the set point temperature is satisfied.
To return the temperature to °F press the "mode" and "-" button simultaneously with the remote in the OFF
position.
Note:
The above differential set is only available for the WALL MOUNTED indoor units.
We recommend having the differential set by professional personnel and setting the temperature at 1
℃
.