4.2.
Operation
When the running speed of the generating set has stabilised (approximately 3 minutes):
n
Check that the circuit breaker is connected.
o
Connect the plug(s) to the generating set socket(s).
4.3.
Switching off
Warning
When the generating set is turned off, the engine continues to give off heat.
Appropriate ventilation should be provided after the generating set is turned off.
To stop the generating set urgently, place the engine switch on "
OFF".
n
Take the plugs out of the sockets and allow the engine to run without any charge for 1 to 2 minutes.
o
Place the engine switch (no. 2, Diag. D) on "
OFF"
and the set will stop.
p
Close the fuel tap (no. 1, Diag. D).
5.
Safety features (if fitted, see specifications table)
5.1.
Oil cut-out
This mechanism is designed to prevent any damage to the motor resulting from lack of oil in the motor sump. It automatically cuts out
the motor. If the motor stops and will not restart, check the motor oil level before looking for any other cause of the problem.
5.2.
Circuit breaker
The electrical circuit of the set is protected by several magnetothermal, differential or thermal cut-out switches. Any overload and/or
short circuits cause the supply of electrical energy to be cut.
6.
Maintenance schedule
6.1.
Reminder of use
The maintenance interval frequency and the operations to be carried out are outlined in the maintenance programme.
However, it should be added that it is the environment in which the generating set is operating which determines this programme.
Accordingly, if the set is used in extreme conditions, shorter intervals between maintenance procedures should be adopted.
These maintenance schedules apply only to generating sets running on fuel and oil, that conform to the specifications given in this
booklet.
6.2.
Maintenance table
Carry out the maintenance procedures
at whichever deadline
is reached first
Part
Each time it is
used
After the
first 8 hours
of use
Every 3
months or
50 hours
Every 6
months or
100 hours
Every 12
months
Check the level
•
Engine oil
Change
(1)
•
Check
•
Air filter
Clean
•
Spark plugs
Check / clean
•
Spark arrester
Clean
•∗
Cleaning the generating set
•
Valves *
Check / adjust
Once per year
Note:
* this procedure should be carried out by one of our registered agents
(1): The engine oil must be changed after the first 8 hours of operation and then in accordance with the maintenance schedule.
7.
Maintenance procedures
7.1.
Cleaning the air filter
Danger
Never use petrol or flammable solvents for cleaning the air filter element as this could result in a fire or
explosion.
n
Remove air filter cover (no. 1, diag H) by undoing screw (no. 2, diag H).
o
Remove pre-filter (no. 3, diag H) and then cartridge (no. 4,diag H)
p
Wash the pre-filter with a solution of domestic detergent and warm water. Leave to dry fully.
q
Gently tap the cartridge several times on a hard surface to remove any excess dirt. Never try to remove dirt using a brush. This
will just push the dirt into the fibres. Replace the paper element if it is too dirty.
r
Refit the air filter elements and cover (no. 1, diag H) in the reverse order of removal, and then tighten mounting bolt (no. 2, diag
H).
Summary of Contents for VX170/4I
Page 2: ...2 4 A A 3 5 4 13 1 2 5 9 15 11 4 10 14 3 22 8 12 6 7...
Page 3: ...3 4 A B C D 1 1 3 2 4 2 1 20 16 19 21 18 17...
Page 4: ...4 4 E F G H 2 1 3 1 2 3 4 2 1...
Page 61: ...1 2 3 4 5 6 7 8 9 10 11 12 13 14 1 1 1 1 2 1 2 3 1 2 3 A B C D E F G H I J K 1 3 1 3 1...
Page 62: ...1 3 2 1 3 3 1 60245 4 IEC 1 3 4 1 3 5...
Page 65: ...4 2 3 n o 4 3 OFF n o OFF 2 D p 1 D 5 5 1 5 2 6 6 1 6 2 8 3 50 6 100 12 1 1 8...