EA Series Operational Modes:

Wiring Example #1 – Non-latching (auto-resetting) Exit Alarm or Door Prop Alarm

.

Opening 

the door will initiate the pre-alarm timer.  Closing the door before the timer expires resets the 
timer.  If the door remains open and the timer expires, an audible alarm will sound and the 
Main Relay will trigger.  Alarm resets on door closure.  Bypass the alarm by activating the 
integral key switch or via remote bypass switch.

(a) All jumpers are set OFF (default)
(b) Adjust the alarm delay timer (1-60 seconds), as required.
(c) Install & terminate a N/C door contact.
(d) Install & terminate optional output relays, as needed.  See page 2 for relay descriptions.
(e) Apply power & test.

12 or 24VDC

P.S.

Key Switch Operation (EA-708 or 728 only):

Bypass (Maintained) –
90° Counter-clockwise.  
Key may be removed. Return to 
vertical position to re-secure.
Alarm Reset (Momentary) –
45° Clockwise.  Key returns to 
vertical position upon release.  

By

pa

ss

Re

se

t

By

pa

ss

Re

se

t

EA-728

EA-708

See Page 5 for Mortise Key Cylinder 
installation

Bypass (Maintained) –
Turn counter-clockwise until ON/OFF 
switch is activated.  Reactivate the 
switch to re-secure.
Alarm Reset (Momentary) –
Turn clockwise until momentary 
switch is activated.

NOTE:  Unit must be Secure to be Bypassed.  Door must be closed to reset an alarm condition.

LED Status Indicator:

N/C

N/O

EA-SN

: Optional Remote Bypass;

Pre-wired for model 

EA-728

Door Contact:

SDC Model MC-4

or similar

Alarm Relay for
remote monitoring

Power Supply:

SDC Model TR-12, TR-24, or 600 Series

Auxiliary Relay follow DPS input

P:\INSTALLATION INST\Accessories\INST-DOOR PROP.vsd      Rev A               07-17     Page  3

G

G

R

G

G

Door Status

Unit Condition

LED Status

Main Relay

Aux. Relay* 

(Jumper 5 OFF)

Aux. Relay 

(Jumper 5 ON)

Closed

Secure

Solid Green

Energized

De-energized

Energized

Open

Pre-alarm (1-60 sec.) Solid Green

Energized

Energized

Energized

Open

Alarm

Solid Red

De-energized

Energized

De-energized

Closed

Bypassed

Flashing Green

Energized

De-energized

De-energized

Open

Bypassed

Flashing Green

Energized

Energized

De-energized

*Relay state shown with N/C Door Contact