43
6.
inBUilt into iSlanD Wall
300mm
below
Ceiling
CaVity lid
to be fully
sealed to
all edges.
15°
step 12: CaVity lid
**important**
side Vents
it is highly recommended the cavity lid be installed flat to
ensure sufficient air flow around the appliance.
front Vents
it is highly recommended the cavity lid be installed on an angle
of 15° facing the front of the fireplace, to ensure sufficient air
flow around the appliance.
the cavity lid must be installed 300mm below the ceiling and
be comprised of the following; minimum 0.5mm thick steel
plate for support, followed by a 12mm thick heat resistant
sheet, with 1 x 25mm rockwool sheet. a hole is to be cut in
the centre of the lid in order for the single skin flue to penetrate
through tightly. You may also use a heat resistance sealant(i.e.
Firecork)and heat proof tape to seal any air gaps.
it is
important to ensure the cavity lid is fully sealed to all edges.
step 11: duCting
the duct must be 4 Zero type(aluminium inner core,
aluminium outer, poly insulated, minimum ri.0) and tested to
as 4254.1-2012. outlet must be metal.
This unit has been supplied with a ducting kit (consisting
of two ducts and two metal registers), while it is highly
recommended that it be installed, if not installed it will have no
implication on the functioning of the unit.
cut a hole in the lid of the enclosure nearest to the room where
the heat is to be transferred. run the ducting from this hole into
the roof space and locate to the room, cut out the plaster and
install a metal register into the ceiling of the desire room.
*
*Please note: a maximum duct run of 6m is recommended
for effective heat transfer,. Please note if an in-line fan is
fitted to the ducting kit, then an Outdoor Air Kit is obligatory
and Must be installed to the unit. an in line fan Cannot be
installed in any axis double sided unit.
fan must be metal, not plastiC.
step 13: side walls
attach a heat resistant material from the base to the top of the
ceiling on the sides of the enclosure.
side Vents
if you are installing your appliance with side vents, ensure you
leave the necessary gaps when constructing the side walls.
(Refer to step 12 & 18)