SCOTTY SS – INSTRUCTION MANUAL
Scotty SS
Nov-05
14
2.5 Clearances
(Fig S202-1)
The KERR SCOTTY SS Wood Furnace is to be installed in accordance with National
Building Code or local regulations. Allowances front and rear must be made for
cleaning and servicing.
NOTE:
Regardless of minimum clearances to combustibles for safety reasons, a
minimum clearance of 30 inches (765 mm) should be allowed at the furnace
rear for cleaning (due to length of cleaning rake) and access to smoke pipe.
Minimum safety clearances to combustibles are:
Front
48”
1220 mm
One Side
6”
152 mm
Other Side (for rear access)
24”
610 mm
Rear (see Note above)
24”
610 mm
Flue Pipe to combustible, other furnace & electrical wiring
18”
457 mm
Wood Furnace Above Plenum and 6’(1.8 m) of duct
6”
152 mm
Supply Duct beyond 6’
2”
50 mm
Return Duct Plenum and 6’(1.8 m) of duct on solid fuel burning warm air furnaces
3”
76 mm
This clearance will also allow adequate combustion air to reach the furnace.
WARM AIR DUCT and PLENUM CLEARANCES
The following clearances must be observed and must meet all local building, electrical
and fire codes. Follow the National Standard of Canada, Installation Code for Solid
Fuel Burning Appliances and Equipment, CSA-B365-01; the National Board of Fire
Underwriters and in the US the NFPA codes.
The KERR SCOTTY SS Wood Furnace warm air plenum and first 6ft (1.8 m) of warm
air supply duct in any direction must be installed observing a minimum of 6 inches (152
mm) clearance from the joists or combustible materials. Beyond the first 6ft (1.8 m) of
supply duct, a 2 inches (51 mm) minimum clearance must be maintained between the
warm air supply ducts and all joists or combustible material (See Fig. S202-1).
Return air ducts, including main ducts and branch ducts, on solid fuel burning warm air
furnaces shall be installed to provide at least 3 inches (76 mm) clearance to
combustible construction for the first 6ft (1.8 m) away from the furnace plenum.
This
requirement is not intended to apply to return air ducts serving an oil-fired, gas
fired or electric furnace to which an add-on furnace is connected.
It is recommended that a non-combustible rigid board be fastened on the underside of
the floor joists in the area of the ceiling above the furnace, warm air ducts and smoke
pipe.
Summary of Contents for DB-202A
Page 11: ...SCOTTY SS INSTRUCTION MANUAL Scotty SS Nov 05 10 SECTION 2 INSTALLATION INSTRUCTIONS ...
Page 24: ...SCOTTY SS INSTRUCTION MANUAL Scotty SS Nov 05 23 SECTION 3 ADD ON TO OIL FURNACE ...
Page 29: ...SCOTTY SS INSTRUCTION MANUAL Scotty SS Nov 05 28 SECTION 4 ADD ON TO ELECTRIC FURNACE ...
Page 34: ......
Page 35: ......
Page 36: ......
Page 37: ......
Page 38: ......
Page 39: ......
Page 40: ......
Page 41: ......
Page 42: ......
Page 43: ......
Page 44: ......
Page 45: ......
Page 46: ......
Page 47: ......