Press the ENTER button.
Press the UP or DOWN buttons to select from
1 to 120. For this example, select 22.
Press the DOWN button. NOTE: LEL
applications should never set an alarm
level above 60% LEL.
Press the ENTER button.
Press the UP button.
Press the ENTER button.
Press the UP or DOWN buttons to select from
1 to 120. For this example, select 18. Press
the DOWN button.
For rising gas alarms, set the reset value
below the WARN value as in this example.
For falling gas alarms (oxygen deficiency), set
the reset value above the WARN value.
Press the ENTER button.
Press the UP button.
WARN SET: 25
0 % LEL
0 % LEL