For The Installer:
Cooling Tower Applications:
This unit requires no special modifications for use
on a cooling tower. However, the sizing of the
cooling tower requires the heat of rejection and the
pressure drop across the ice machine’s water
cooling circuit (water regulating valve and
condenser).
·
Heat of Rejection: 27,400 BTUH - Peak
·
Pressure Drop: 7 psi
·
Maximum water temp into condenser: 110
o
F.
·
Peak GPM at 110
o
F: 9 - 10
·
GPH at 110/100: 372
·
GPH at 90/70: 107
·
GPH at 70/50: 59
CME1856W