EN
OEM Manual – CUBO
2
AQUA
UMT/WG T BT Rev3.0 – 08/10/2021
Pag. 31-EN
Mask
index
Topic
Description
Serious
alarm
Normal
alarm
Action
Delay
Reset
60
minutes)
ALP04
Parallel compressor envelop alarm.
Compressor is working out of
admitted envelope. The current
operating zone is reported in the
same mask
x
Shut Off Parallel
compressor
Settable
by mask
Cbg55
Automatic
ALP05
Parallel compressor high discharge
gas temperature.
Discharge temperature measured
by the probe is higher than the
Alarm threshold set on mask Cag57
x
Shut Off Parallel
compressor
No delay Automatic
ALP06
Parallel compressor low pressure
differential (insufficient lubrication).
The pressure difference between
suction and discharge of parallel
compressor is too low.
x
Compressor Shut off
Settable
by mask
Cbg55
Automatic
ALP07
Parallel compressor inverter model
not compatible (power+ only
allowed).
The inverter model is not
compatible with the compressor
size configured on mask Cag12
x
Parallel compressor does
not start
No delay Automatic
ALW40-
53-66-
79-92
EV
A
PO
R
A
TO
R
S
Store number: !! OFFLINE !!
x
-
Not present
R2
2
ALW41-
54-67-
80-93
Store number: Low temperature
alarm [Generic Probe 1]
x
Display only (refer to
MPXPRO / Ultracella user
manual)
ALW42-
55-68-
81-94
Store number: High temperature
alarm [Generic Probe 1]
x
Display only (refer to
MPXPRO / Ultracella user
manual)
ALW43-
56-69-
82-95
Store number: Low temperature
alarm [Generic Probe 2]
x
Display only (refer to
MPXPRO / Ultracella user
manual)
ALW44-
57-70-
83-96
Store number: High temperature
alarm [Generic Probe 2]
x
Display only (refer to
MPXPRO / Ultracella user
manual)
ALW45-
58-71-
84-97
Store number: Defrost timeout
x
Display only (refer to
MPXPRO / Ultracella user
manual)
ALW46-
59-72-
85-98
Store number: Low superheat
alarm
x
Display only (refer to
MPXPRO / Ultracella user
manual)
ALW47-
60-73-
86-99
Store number: Low suction
temp.alarm
x
Display only (refer to
MPXPRO / Ultracella user
manual)
ALW48-
61-74-
87-
ALZ00
Store number: MOP alarm
x
Display only (refer to
MPXPRO / Ultracella user
manual)
ALW49-
62-75-
88-
ALZ01
Store number: LOP alarm
x
Display only (refer to
MPXPRO / Ultracella user
manual)
Summary of Contents for Cuno 2 Aqua
Page 2: ......
Page 46: ......
Page 62: ...DE OEM HANDBUCH CUBO2 AQUA Seite 16 DE UMT WG T BT Rev3 0 08 10 2021...
Page 134: ......
Page 136: ...Notes Anmerkungen Remarques...
Page 137: ......