Debounce:
It is n
ecessary to configure a debounce time for edge detection. The debounce is the sensor stabilization time - the minimum time at
which the sensor must remain at the logical level of interest so that the detected edge is considered valid. The minimum configurable debounce
time is 50 milliseconds and the maximum are 6 seconds. The device will only register the event after the end of the debounce time. Thus, the
event will be logg
ed with a delay equal to the debounce time.
9.3.4 CHANNELS GENERAL PARAMETERS
NXperience
NXperience Mobile
Android
iOS
Figure 12 –
Channels General Parameters
•
Alar
m Buzzer Runtime:
Allows you to configure the buzzer runtime for each time the device enters an alarm situation. The configuration is
performed in seco
nds, from 0 to 65000 s, where 0 means that the buzzer should not be triggered.
•
Po
wer Line Frequency:
Must be set to the frequency of the local power line (50 Hz or 60 Hz) for the device to perform better.
●
Digital
Output Mode:
Allows you to configure the digital output mode. The digital output can be configured to Disabled, Auxiliary E
lectronic
Switch, or Alarm Status.
o
Auxiliary Electronic Switch:
Controls the power supply of external instruments during analog channel readings.
Drive Ti
me:
Allows you to configure, in seconds, how long before each acquisition the digital output must be triggered. The mini
mum
configurable time is 0 seconds and the maximum time is 15 minutes (900 seconds). If equal to 0, the Auxiliary Electronic Switch will be
enabled at the exact moment of an acquisition. If greater than or equal to the lowest acquisition interval, the Auxiliary Electronic Switch
will always be enabled.
o
Alarm Status:
In this mode, the Digital Output will follow the current general alarm status. If any channel is in an alarm situation, the digital
output is triggered. If no channel is set to alarm, the di
gital output is disabled.
9.3.5 DATA LOGGING CONFIGURATION
NXperience
NXperience Mobile
Android
iOS
Figure 13 –
Logs
LOGS
•
Log Data:
Allows you to enable or disable data registering on the device.
•
Log Interval:
Allows the user to select the frequency, in seconds, with which an acquisition must be made and logged in the memory.
○ Minimum Interval:
■ 1 second (if no channel is configured to operate on average);
■ 10 seconds (if a channel is configured to operate on average).
27/65