3-36
Overcurrent, Voltage, Synchronism Check, and Frequency Elements
Date Code 990430
SEL-351P Manual Técnico
If the voltages are not static (voltages slipping with respect to one another), the two synchronism
check elements operate as shown in the bottom of Figure SECTION 3: .23. The angle difference
is compensated by breaker close time, and the breaker is ideally closed at a zero degree phase
angle difference, to minimize system shock.
These synchronism check elements are explained in detail in the following text.
Synchronism Check Elements Settings
Table SECTION 3: .9: Synchronism Check Elements Settings and Settings Ranges
Setting Definition
Range
25VLO
low voltage threshold for “healthy voltage”
window
0.0 - 150.0 V secondary
25VHI
high voltage threshold for “healthy voltage”
window
0.0 - 150.0 V secondary
25SF
maximum slip frequency
0.005 - 0.500 Hz
25ANG1
synchronism check element 25A1 maximum
angle
0° - 80°
25ANG2
synchronism check element 25A2 maximum
angle
0° - 80°
SYNCP
synchronizing phase
VA, VB, or VC
TCLOSD
breaker close time for angle compensation
0.00 - 60.00 cycles
BSYNCH SEL
OGIC
Control Equation block synchronism
check setting
Relay Word bits referenced
in Table 9.3
Accuracy
Voltage Pickup:
±
1 V and
±
5% of setting
Voltage Transient Overreach:
±
5% of setting
Slip Pickup:
0.003 Hz
Angle Pickup:
±
2
°
Summary of Contents for SEL-351P
Page 6: ......
Page 92: ......
Page 96: ......
Page 154: ......
Page 156: ......
Page 222: ......
Page 258: ......
Page 262: ......
Page 324: ......
Page 368: ......
Page 406: ......
Page 482: ......
Page 534: ......
Page 539: ......
Page 549: ......
Page 551: ......
Page 587: ......
Page 597: ......
Page 601: ......
Page 603: ......
Page 609: ......
Page 621: ......
Page 635: ......
Page 649: ......
Page 665: ......
Page 671: ......