9.41
Date Code 20120126
Instruction Manual
SEL-2032 Communications Processor
Protocols
Serial Distributed Network Protocol (Serial DNP3)
**>
AUTO 3
FID: FID=SEL-421-R100-V0-Z001001-D20010703
DEVICE ID: Relay 1
BAUD RATE: 9600
OPERATE SUPPORT: Binary (2 Breakers, 32 Remote Bits S-C-P)
SER SUPPORT: Binary Unsolicited
COMMANDS SUPPORTED:
B 20METER
B 20DEMAND
B 20TARGET
A 20STATUS
A 20BREAKER
A 20EVENTL
Figure 9.5
Example AUTO Command Response for Device That Supports
Fast SER
Proceed with the following steps to use Fast SER to provide SER quality
DNP3 event time stamps for the circuit breaker position contact (52a) from an
SEL-421 Relay connected to Port 3:
Step 1. Connect the SEL-421 Relay to the SEL-2032 with a cable that
provides both data and IRIG connections (C273A) or a data
cable (C272A) and a directly connected IRIG source.
Step 2. Configure Port 3 of the SEL-2032 to communicate with an SEL
IED and select Yes when prompted to start an
autoconfiguration.
Step 3. Perform an
AUTO 3
command on the SEL-2032 and you will
see a response similar to that in
indicating that Fast
SER data is available.
Step 4. Configure the SEL-421 SER function to monitor the circuit
breaker position contact called 52AA1 inside the relay.
Step 5. Configure automatic messaging for the SEL-2032 Port 3 to
collect 20TARGET data.
This data will act as present state data during SEL-2032
initialization.
Step 6. Configure the SEL-2032 Port 16 for DNP3 using the
appropriate parameters for your DNP3 master device.
You must enable event data by setting the Event Class setting
CLASS to 1, 2, or 3.
Step 7. Enter the following math/movement statement on Port 16:
0:0 = 3:STATE:52AA1
Step 8. Collect event data with the DNP3 master.
If a trip-reclose-trip event occurs with the circuit breaker
connected to the SEL-421, the DNP3 master will receive three
time-stamped events, one for each circuit breaker trip and
close.
To collect the same data from the SEL-421 shown on Port 1 of the lower tier in
, follow the additional steps below:
Step 9. Connect the SEL-421 to the lower-tier SEL-2032 with a cable
that provides both data and IRIG connections (C273A) or a
data cable (C272A) and a directly connected IRIG source.
Step 10. Configure Port 1 of the lower-tier SEL-2032 to communicate
with an SEL IED and select Yes when prompted to start an
autoconfiguration.
Summary of Contents for SEL-2032
Page 6: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 12: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 46: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 70: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 104: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 124: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 188: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 216: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 244: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 322: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 328: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 336: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 338: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 342: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 348: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 354: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...