10.11
Date Code 20080918
Instruction Manual
SEL-749M Relay
Testing and Troubleshooting
Self-Test
Self-Test
The SEL-749M runs a variety of self-tests. Two Relay Word bits, HALARM
and SALARM, signal self-test problems. SALARM is pulsed for software-
programmed conditions; these include settings changes, access level changes,
and three consecutive unsuccessful password entry attempts. HALARM is
pulsed for hardware self-test warnings. HALARM is continuously asserted
(set to logical 1) for hardware self-test failures. A diagnostic alarm may be
configured as explained in
Section 4: Protection and Logic Functions
.
lists hardware self-tests. In the
Alarm Status
column,
Latched
indicates that HALARM is continuously asserted,
Not Latched
indicates that
HALARM is pulsed for 5 seconds, and
NA
indicates that HALARM is not
asserted.
All hardware self-test failures generate a front-panel message that is
automatically sent to the serial port. All hardware self-test failures (
Latched
entry in
Alarm Status
column) disable the relay.
Table 10.8
Relay Self-Tests
(Sheet 1 of 2)
Self-Test
Description
Limits
Protection
Disabled on
Failure
Alarm
Status
Front-Panel Message
on Failure
External RAM
(power up)
Performs a read/write test on
system RAM
Yes
Latched
Status Fail
RAM Failure
External RAM
(run time)
Performs a read/write test on
system RAM
Yes
Latched
Status Fail
RAM Failure
Internal RAM
(power up)
Performs a read/write test on
CPU RAM
Yes
Latched
Status Fail
RAM Failure
Internal RAM
(run time)
Performs a read/write test on
CPU RAM
Yes
Latched
Status Fail
RAM Failure
Critical RAM
(settings)
Performs a checksum test on
the active copy of settings
Checksum
Yes
Latched
Status Fail
CR_RAM Failure
Code RAM
(run time)
Verify instruction matches
FLASH image
Yes
Latched
Status Fail
CR_RAM Failure
Code Flash
(power up)
SEL
BOOT
qualifies code with a
checksum
Checksum
NA
NA
Code Flash
(run time)
Checksum is computed on the
entire code base
Checksum
Yes
Latched
Status Fail
ROM Failure
Data Flash
(power up)
Checksum is computed on crit-
ical data
Checksum
Yes
Latched
Status Fail
Non_Vol Failure
Data Flash
(run time)
Checksum is computed on crit-
ical data
Checksum
Yes
Latched
Status Fail
Non_Vol Failure
Front Panel
(power up)
Fail if ID registers do not
match expected or if FPGA
programming is unsuccessful
No
Not Latched
I/O Board Failure
Check if ID register matches
part number
Yes
Latched
Status Fail
I/O Card Failure
DeviceNet
Board Failure
DeviceNet card does not
respond in three consecutive
300 ms time out periods
NA
NA
COMMFLT
Warning
Summary of Contents for SEL-749M
Page 6: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 14: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 20: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 32: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 52: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 118: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 188: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 216: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 224: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 274: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 286: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 306: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 310: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 314: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...