701 Motor Protection Relay
Date Code 20010719
Settings Calculation
Basic Motor Protection
4.26
Load-Loss Elements
Load-Loss Element, No Voltage Option (Relay Models 0701000X & 0701010X)
Table 4.17
Load-Loss Element Settings, No Voltage Option
When the relay is not equipped with optional voltage inputs, the load-loss
detection function is dependent on current alone. The relay arms the load-loss
detection logic a settable time after the motor starts, as defined by the Load Loss
Starting Time Delay setting. Set this delay to allow pumps or compressors to reach
normal load. Once armed, the function issues an alarm or trip if phase current drops
below the alarm or trip threshold for the specified time delay.
Set the Load Loss Trip and Alarm thresholds greater than the expected motor no
load current but less than the minimum current expected when the motor is operating
normally. These settings are entered in per unit of the Full Load Amps (FLA) setting.
If you expect the motor to operate at no load normally, disable this function by
setting LLAPU equal to OFF. The relay automatically hides the remaining load-loss
settings.
Load-Loss Element, Voltage
Option Included (Relay Models 0701001X & 0701011X)
Table 4.18
Load-Loss Element Settings, With Voltage Option
Table 4.17
Load-Loss Element Settings, No Voltage Option
Setting Prompt
Setting Range
Setting Name =
Factory Default
Load Loss Alarm Threshold
OFF, 0.10–1.00 pu FLA
LLAPU = OFF
Load Loss Trip Threshold
0.10–1.00 pu FLA
LLTPU = 0.50
Load Loss Starting Time Delay
0–15000 s
LLSDLY = 0
Load Loss Alarm Time Delay
0.00–400.00 s
LLADLY = 5.00
Load Loss Trip Time Delay
0.00–400.00 s
LLTDLY = 10.00
Table 4.18
Load-Loss Element Settings, With Voltage Option
Setting Prompt
Setting Range
Setting Name =
Factory Default
Load Loss Alarm Threshold
OFF, 30–2000 W
a
LLAPU = OFF
Load Loss Trip Threshold
30–2000 W
a
LLTPU = 0.50
Load Loss Starting Time Delay
0–15000 s
LLSDLY = 0
Load Loss Alarm Time Delay
0.00–400.00 s
LLADLY = 5.00
Load Loss Trip Time Delay
0.00–400.00 s
LLTDLY = 10.00
a
Setting range shown for ITAP = 5 A. Range is 6–400 W when ITAP = 1 A.
Summary of Contents for SEL-701
Page 12: ...This page intentionally left blank ...
Page 18: ...This page intentionally left blank ...
Page 20: ...This page intentionally left blank ...
Page 36: ...This page intentionally left blank ...
Page 64: ...This page intentionally left blank ...
Page 144: ...This page intentionally left blank ...
Page 198: ...This page intentionally left blank ...
Page 232: ...This page intentionally left blank ...
Page 246: ...This page intentionally left blank ...
Page 346: ...This page intentionally left blank ...
Page 390: ...This page intentionally left blank ...
Page 408: ...This page intentionally left blank ...
Page 410: ......
Page 412: ......
Page 414: ......
Page 416: ......
Page 418: ......
Page 420: ......
Page 422: ......
Page 424: ......
Page 426: ......
Page 428: ......
Page 430: ......
Page 432: ......
Page 434: ......
Page 436: ......
Page 438: ......
Page 440: ......
Page 442: ......
Page 452: ...This page intentionally left blank ...