701 Motor Protection Relay
Date Code 20010719
SEL
OGIC®
Control Equations & Relay Logic
Breaker Auxiliary Contact SEL
OGIC
Control Equation Setting
B.22
Breaker Auxiliary Contact
SEL
OGIC
Control Equation Setting
The breaker auxiliary contact SEL
OGIC
control equation setting, 52A =, defines
the relay input contact that is connected to a breaker auxiliary contact. The factory
default setting, 52A = !IN1, allows you to connect a breaker 52B contact to input IN1.
If you wish to connect a breaker 52A contact to the input, set 52A = IN1. The equation
result is the 52A Relay Word bit. You can use the result to create custom control
functions such as breaker failure logic, if necessary, for your application.
Summary of Contents for SEL-701
Page 12: ...This page intentionally left blank ...
Page 18: ...This page intentionally left blank ...
Page 20: ...This page intentionally left blank ...
Page 36: ...This page intentionally left blank ...
Page 64: ...This page intentionally left blank ...
Page 144: ...This page intentionally left blank ...
Page 198: ...This page intentionally left blank ...
Page 232: ...This page intentionally left blank ...
Page 246: ...This page intentionally left blank ...
Page 346: ...This page intentionally left blank ...
Page 390: ...This page intentionally left blank ...
Page 408: ...This page intentionally left blank ...
Page 410: ......
Page 412: ......
Page 414: ......
Page 416: ......
Page 418: ......
Page 420: ......
Page 422: ......
Page 424: ......
Page 426: ......
Page 428: ......
Page 430: ......
Page 432: ......
Page 434: ......
Page 436: ......
Page 438: ......
Page 440: ......
Page 442: ......
Page 452: ...This page intentionally left blank ...