SEL-701-1 Monitor
Date Code 20011009
SEL-2020/SEL-2030 Compatibility Features
Fast Binary Message Definitions
D.4
A5C1 Fast Meter Configuration Block
In response to the A5C1 request, the SEL-701-1 Monitor sends the block shown
in
.
Table D.4
A5C1 Fast Meter Configuration Block
(Sheet 1 of 5)
Data
Description
A5C1
Fast Meter command
xx
Response Length in Bytes
(specific value of xxbased
on monitor model, as shown below)
0x6C
Base Monitor
0x94
Monitor with RTDs
0xD0
Monitor with voltages
0xF8
Monitor with RTDs, voltages
01
One status flag byte
00
Scale factors in Fast Meter message
00
No scale factors
xx
# of analog input channels
(specific value of xxbased
on monitor model, as shown below)
09
Base Monitor
0D
Monitor with RTDs
13
Monitor with voltages
17
Monitor with RTDs, voltages
01
# of samples per channel
16
# of digital banks
00
# of calculation blocks
0004
Analog channel offset
xxxx
Time stamp offset
(specific value of xxxx based on
monitor model, as shown below)
0028
Base Monitor
0030
Monitor with RTDs
0050
Monitor with voltages
0058
Monitor with RTDs, voltages
Summary of Contents for SEL-701-1
Page 16: ...This page intentionally left blank ...
Page 18: ...This page intentionally left blank ...
Page 20: ...This page intentionally left blank ...
Page 34: ...This page intentionally left blank ...
Page 118: ...This page intentionally left blank ...
Page 142: ...This page intentionally left blank ...
Page 196: ...This page intentionally left blank ...
Page 210: ...This page intentionally left blank ...
Page 242: ...This page intentionally left blank ...
Page 384: ...This page intentionally left blank ...