D.28
SEL-700G Relay
Instruction Manual
Date Code 20170814
DNP3 Communications
DNP3 Documentation
Figure D.6
Analog Input Map Entry in QuickSet Software
Figure D.7
AI Point Label, Scaling, and Dead Band in QuickSet
The SET DNP x CO_00 <Enter> command allows you to populate the DNP
counter map with per-point dead bands. Entering these settings is similar to
defining the analog input map settings.
You can use the command SET DNP x BO_00 TERSE <Enter> to change
the binary output map x as shown in Figure D.8. You can populate the custom
BO map with any of the 32 remote bits (RB01–RB32). You can define bit
pairs in BO maps by including a colon (:) between the bit labels.
=>>
SET DNP 1 BO_00 TERSE <Enter>
Binary Output Map
DNP Binary Output Label Name (23 characters)
BO_00 := NA
? >
RB01 <Enter>
DNP Binary Output Label Name (23 characters)
BO_01 := NA
? >
RB02 <Enter>
DNP Binary Output Label Name (23 characters)
BO_02 := NA
? >
RB03:RB04 <Enter>
DNP Binary Output Label Name (23 characters)
BO_03 := NA
? >
RB05:RB06 <Enter>
DNP Binary Output Label Name (23 characters)
BO_04 := NA
? >
end <Enter>
=>>
Figure D.8
Sample Custom DNP3 BO Map Settings
Summary of Contents for SEL-700G Series
Page 14: ...This page intentionally left blank ...
Page 22: ...This page intentionally left blank ...
Page 32: ...This page intentionally left blank ...
Page 52: ...This page intentionally left blank ...
Page 106: ...This page intentionally left blank ...
Page 510: ...This page intentionally left blank ...
Page 560: ...This page intentionally left blank ...
Page 578: ...This page intentionally left blank ...
Page 588: ...This page intentionally left blank ...
Page 604: ...This page intentionally left blank ...
Page 634: ...This page intentionally left blank ...
Page 738: ...This page intentionally left blank ...
Page 802: ...This page intentionally left blank ...