Testing and Troubleshooting
Commissioning Tests
Figure 10.3
Three-Phase Wye AC Connections
Figure 10.4
Three-Phase Open-Delta AC Connections
Step 11. Apply rated current (1 A or 5 A).
If the relay is equipped with voltage inputs, apply rated voltage
for your application.
Step 12. Use the front-panel
METER > Fundamental
function or serial
port METER command to verify that the relay is measuring
the magnitude and phase angle of both voltage and current
correctly, taking into account the relay PTRX, PTRY, PTRS,
+120˚
–120˚
V
C
V
B
V
C
V
A
PHROT := ABC
+120˚
–120˚
PHROT := ACB
V
B
V
A
When setting PHROT := ABC, set angle V
A
= angle I
A
= 0˚
set angle V
B
= angle I
B
= —120˚
set angle V
C
= angle I
C
= 120˚
When setting PHROT := ACB, set angle V
A
= angle I
A
= 0˚
set angle V
B
= angle I
B
= 120˚
set angle V
C
= angle I
C
= —120˚
60˚
V
AB
V
CB
PHROT := ABC
60˚
V
AB
V
CB
PHROT := ACB
When setting PHROT := ABC, set angle I
A
= 0˚
set angle I
B
=
—120˚
set angle I
C
= 120˚
set angle V
AB
= +30˚
set angle V
CB
= +90˚
When setting PHROT := ACB, set angle I
A
= 0˚
set angle I
B
= 120˚
set angle I
C
=
—120˚
set angle V
AB
= —30˚
set angle V
CB
= —90˚
Summary of Contents for SEL-700G Series
Page 14: ...This page intentionally left blank ...
Page 22: ...This page intentionally left blank ...
Page 32: ...This page intentionally left blank ...
Page 52: ...This page intentionally left blank ...
Page 106: ...This page intentionally left blank ...
Page 510: ...This page intentionally left blank ...
Page 560: ...This page intentionally left blank ...
Page 578: ...This page intentionally left blank ...
Page 588: ...This page intentionally left blank ...
Page 604: ...This page intentionally left blank ...
Page 634: ...This page intentionally left blank ...
Page 738: ...This page intentionally left blank ...
Page 802: ...This page intentionally left blank ...