SEL-421 Relay
Metering, Monitoring, and Reporting
Metering
Relay Word bits PF
_OK and DPF
_OK are provided to indicate that the infor-
mation coming into the relay is sufficient to provide a valid power factor mea-
surement. The per-phase power factor bit, PF
_OK, is equal to 1 if the measured
per-phase rms voltage, V
rms
, is greater than 10 percent of the nominal voltage
setting and the relay does not detect an open-phase condition. Otherwise,
PF
_OK = 0. Similarly, for the per-phase displacement power factor check,
DPF
_OK, is equal to 1 if the magnitude of the per-phase fundamental voltage,
V
FM, is greater than 10 percent of the nominal voltage setting and the relay
does not detect an open-phase condition. Otherwise, DPF
_OK = 0.
High-Accuracy Instantaneous Metering
The SEL-421 is a high-accuracy metering instrument. See
the SEL-400 Series Relays Instruction Manual
for details of the accuracy and
how to calculate error coefficients.
Maximum/Minimum Metering
Maximum/Minimum Metering on page 7.5 in the SEL-400 Series Relays
Instruction Manual
for a complete description of using and controlling maxi-
mum/minimum metering.
The SEL-421 provides maximum/minimum metering for LINE input rms volt-
ages, rms currents, rms powers, and frequency; it also conveys the maximum/
minimum rms currents for circuit breakers BK1 and BK2, as well as both dc bat-
tery voltage maximums and minimums. The SEL-421 also records the maximum
values of the sequence voltages and sequence currents.
lists these quan-
tities.
Three-phase true apparent power
3U
rms
X
Per-phase displacement power factor
PF
1
X
Per-phase true power factor
PF
X
Three-phase displacement power factor
3PF
1
X
Three-phase true power factor
3PF
X
Table 7.3
Instantaneous Metering Quantities—Power (Sheet 2 of 2)
Metered Quantity
Symbol
Fundamental
(50 Hz/
60 Hz Only)
RMS
(Harmonics
Included)
Table 7.4
Maximum/Minimum Metering Quantities—Voltages, Currents,
Frequency, and Powers (Sheet 1 of 2)
Metered Quantity
Symbol
RMS phase voltage
V
rms
RMS phase current
I
rms
Positive-sequence voltage magnitude
a
|V
1
|
Negative-sequence voltage magnitude
|3V
2
|
Zero-sequence voltage magnitude
|3V
0
|
DC battery voltage
VDC1, VDC2
Positive-sequence current magnitude
|I
1
|
Negative-sequence current magnitude
|3I
2
|
Zero-sequence current magnitude
|3I
0
|
Summary of Contents for SEL-421-4
Page 6: ...This page intentionally left blank ...
Page 14: ...This page intentionally left blank ...
Page 30: ...This page intentionally left blank ...
Page 104: ...This page intentionally left blank ...
Page 128: ...This page intentionally left blank ...
Page 536: ...This page intentionally left blank ...
Page 584: ...This page intentionally left blank ...
Page 616: ...This page intentionally left blank ...
Page 696: ...This page intentionally left blank ...
Page 750: ...This page intentionally left blank ...
Page 755: ...Instruction Manual PM400 01 NB SEL 400 Series Relays Instruction Manual 20171006 ...
Page 776: ...This page intentionally left blank ...
Page 932: ...This page intentionally left blank ...
Page 976: ...This page intentionally left blank ...
Page 1024: ...This page intentionally left blank ...
Page 1038: ...This page intentionally left blank ...
Page 1064: ...This page intentionally left blank ...
Page 1128: ...This page intentionally left blank ...
Page 1206: ...This page intentionally left blank ...
Page 1316: ...This page intentionally left blank ...
Page 1350: ...This page intentionally left blank ...
Page 1464: ...This page intentionally left blank ...
Page 1468: ...This page intentionally left blank ...
Page 1492: ...This page intentionally left blank ...
Page 1518: ...This page intentionally left blank ...