7.5
Date Code 20171006
Instruction Manual
SEL-400 Series Relays
Metering
Maximum/Minimum Metering
Maximum/Minimum Metering
The relay measures and retains the deviations of the power system since the last
maximum/minimum reset. Knowing these maximum and minimum quantities
can help you operate your power system more effectively in a variety of ways.
For example, you can benefit from maximum/minimum metering information by
using it to track power flow for troubleshooting, planning future expansion, and
scheduling maintenance.
NOTE:
Not all SEL-400 series relays
support maximum/minimum
metering.
The relay provides maximum/minimum metering for a variety of line and breaker
quantities, as well as for dc battery voltage. The relay also records the maximum
values of the sequence voltages and sequence currents.
View or Reset Maximum/Minimum Metering Information
The relay shows time stamped maximum/minimum quantities when you use a
communications port or
AC
SEL
ERATOR
QuickSet SEL-5030 Software to view
these quantities. In addition, you can read the maximum/minimum quantities on
the relay front-panel LCD screen.
To reset the maximum/minimum values, use the
MET RM
command from a
communications terminal, or use the
RESET
button in the QuickSet
HMI > Meter
and Control > Maximum/Minimum
window, or answer
Y
and press
ENT
at the
Maximum/Minimum
submenu reset prompt on the front-panel LCD screen. You can
also reset maximum/minimum metering with Global settings (typically RST-
MML, RSTMMB1, and RSTMMB2).
Maximum/Minimum Metering Updating and Storage
The relay updates maximum/minimum values once per power system cycle. The
relay stores maximum/minimum values and the corresponding dates and times to
nonvolatile storage once per day. If greater than a previously stored maximum or
less than a previously stored minimum, the new value overwrites the previous
value. Should the relay lose control power, it will restore the maximum/minimum
information saved at 23:50 hours on the previous day.
The relay updates maximum/minimum values under the following conditions:
➤
DFAULT is deasserted (equals logical 0)
➤
The metering value is greater than the previous maximum, or less
than the previous minimum, for 2 cycles
➤
Voltage input is greater than 13 V secondary
➤
Current input is greater than 0.05 • I
NOM
(in secondary amperes)
Megawatt and megavar maximum/minimum values are subject to the above volt-
age thresholds, current thresholds, and conditions.
When you use
, you add an error amount related to the nominal
current rating of the relay, I
NOM.
Use just the numeric portion of I
NOM
,
either “5” for a 5 A relay or “1” for a 1 A relay; do not use the unit (A). The
errors in
are very small and qualify the relay as a high-accuracy
meter.
Example 7.1
Calculating Exact Error Coefficients (Continued)
Summary of Contents for SEL-421-4
Page 6: ...This page intentionally left blank ...
Page 14: ...This page intentionally left blank ...
Page 30: ...This page intentionally left blank ...
Page 104: ...This page intentionally left blank ...
Page 128: ...This page intentionally left blank ...
Page 536: ...This page intentionally left blank ...
Page 584: ...This page intentionally left blank ...
Page 616: ...This page intentionally left blank ...
Page 696: ...This page intentionally left blank ...
Page 750: ...This page intentionally left blank ...
Page 755: ...Instruction Manual PM400 01 NB SEL 400 Series Relays Instruction Manual 20171006 ...
Page 776: ...This page intentionally left blank ...
Page 932: ...This page intentionally left blank ...
Page 976: ...This page intentionally left blank ...
Page 1024: ...This page intentionally left blank ...
Page 1038: ...This page intentionally left blank ...
Page 1064: ...This page intentionally left blank ...
Page 1128: ...This page intentionally left blank ...
Page 1206: ...This page intentionally left blank ...
Page 1316: ...This page intentionally left blank ...
Page 1350: ...This page intentionally left blank ...
Page 1464: ...This page intentionally left blank ...
Page 1468: ...This page intentionally left blank ...
Page 1492: ...This page intentionally left blank ...
Page 1518: ...This page intentionally left blank ...