14.34
SEL-400 Series Relays
Instruction Manual
Date Code 20171006
ASCII Command Reference
Command Description
If the device supports IEC 61850 and the IEC 61850 protocol is enabled, the
ID
command will display the following additional information.
➤
iedName: the IED name (e.g., SEL-411L_OtterTail)
➤
type: the IED type (e.g., SEL-411L)
➤
configVersion: the CID file configuration version (e.g.,
ICD-411L-R100-V0-Z001001-20060512)
➤
LIB61850ID: an eight-character code indicating the IEC 61850
library version within the product
A sample
ID
command response from the relay (with IEC 61850 enabled) is
shown in
.
IRIG
The
IRIG
command directs the relay to use the next available demodulated
IRIG-B time code to update the relay internal clock. For information on the IRIG
time mode, see
IRIG-B Timekeeping on page 11.1
NOTE:
Not all SEL-400 series relays
support the
IRIG
command.
The
IRIG
command was originally provided in the relay as a testing aid. The
IRIG
command was used to update the relay internal clock with the IRIG-B time
value without waiting for the 30-second confirmation time delay.
There is no longer a 30-second confirmation time delay—the relay uses the IRIG
time source as soon as it determines that the signal is valid, a process that may
take several seconds. Once the IRIG signal is verified, the relay clock is updated
once per second. The
IRIG
command is still available, but is no longer neces-
sary. To check IRIG status, use the
TIME Q
command instead—see
If the relay has no valid IRIG-B time code at the rear panel, or if the
TIME Q
command reports a relay time source other than IRIG or HIRIG, the relay
responds to the
IRIG
command with the following error message,
IRIG-B DATA
ERROR
. See the
TIME
command for more information.
=
ID <ENTER>
"FID=SEL-451-5-R319-V0-Z024013-D20170608","0916"
"BFID=SLBT-4XX-R209-V0-Z001002-D20150130","097C"
"CID=85F4","0264"
"DEVID=Relay 1","0467"
"DEVCODE=40","030B"
"PARTNO=04515415XC4X4H60X0XXX","07B3"
"SERIALNO=1234567890","0517"
"CONFIG=11102200","03EA"
"SPECIAL=000000","03CE"
"iedName=SEL_451_1","05CD"
"type=SEL_451","044C"
"configVersion=ICD-451-R301-V0-Z316006-D20170130","0D1C"
"LIB61850ID=9048BE8A","04EA"
=
Figure 14.6
Sample ID Command Response From Ethernet Card
Table 14.79
IRIG Command
Command
Description
Access Level
IRIG
Lock the relay internal clock to the IRIG-B time code input.
1, B, P, A, O, 2
Summary of Contents for SEL-421-4
Page 6: ...This page intentionally left blank ...
Page 14: ...This page intentionally left blank ...
Page 30: ...This page intentionally left blank ...
Page 104: ...This page intentionally left blank ...
Page 128: ...This page intentionally left blank ...
Page 536: ...This page intentionally left blank ...
Page 584: ...This page intentionally left blank ...
Page 616: ...This page intentionally left blank ...
Page 696: ...This page intentionally left blank ...
Page 750: ...This page intentionally left blank ...
Page 755: ...Instruction Manual PM400 01 NB SEL 400 Series Relays Instruction Manual 20171006 ...
Page 776: ...This page intentionally left blank ...
Page 932: ...This page intentionally left blank ...
Page 976: ...This page intentionally left blank ...
Page 1024: ...This page intentionally left blank ...
Page 1038: ...This page intentionally left blank ...
Page 1064: ...This page intentionally left blank ...
Page 1128: ...This page intentionally left blank ...
Page 1206: ...This page intentionally left blank ...
Page 1316: ...This page intentionally left blank ...
Page 1350: ...This page intentionally left blank ...
Page 1464: ...This page intentionally left blank ...
Page 1468: ...This page intentionally left blank ...
Page 1492: ...This page intentionally left blank ...
Page 1518: ...This page intentionally left blank ...