11.8
SEL-400 Series Relays
Instruction Manual
Date Code 20171006
Time and Date Management
Time Quality Indications
TIME Q Command
The
TIM Q
command provides details about relay timekeeping (see
and
). The internal clock of the relay is initially calibrated at the SEL
factory. An external IRIG or PTP source is required to eliminate clock drift. The
Time Source
field provides the present high-accuracy timing input source;
entries for this line are HIRIG, HPTP, or OTHER. The
Last Update Source
reports the source from which the relay referenced the last time value measure-
ment. Entries for this line can be high-priority or low-priority sources.
lists the possible
Last Update Source
values for the relay.
The
Time Mark Period
value indicates the instantaneous period in which the
relay measures the time-source inputs. The relay displays the time mark periods
showing the present time precision derived from the applied time-source signals.
The
TIME Q
command is also helpful for troubleshooting IRIG and PTP prob-
lems. If the
Time Mark Period
value changes significantly between successive
TIME Q
commands, there may be too much noise in the time signal for the relay
timekeeping function.
=>>
TIM Q <Enter>
Relay 1 Date: 02/24/2016 Time: 15:08:41.468
Station A Serial Number: 0000000000
Time Source: HPTP
Last Update Source: HPTP
Grandmaster Clock Quality
Clock Class : Synchronized with PTP timescale (6)
Time Traceable : TRUE
Clock Accuracy : Within 25 ns
Offset Log Variance : 0
Time Mark Period: 1000.000061 ms
Internal Clock Period: 19.999935 ns
=>>
Figure 11.4
Sample TIM Q Command Response
Table 11.5
Date/Time Last Update Sources
Time Input Source Mode
Priority
Time Source
HIRIG
High
Time/date from the high-accuracy IRIG-B input
SNTP
Low
Simple Network Time Protocol
IRIG
High
Time/date from the IRIG-B format time base signal
HPTP
High
Time/date from a high-accuracy PTP source
PTP
High
Time/date from a PTP source
DNP
Low
Time/date from the DNP3 communications port
MIRRORED BITS
Low
Time/date from the Mirrored Bit port
SNTP
Low
Time/date from SNTP server
ASCII TIME
Low
Time from the relay serial ports
ASCII DATE
Low
Date from the relay serial ports
NONV CLK
Low
Time/date from the nonvolatile memory clock
FRONT PANEL TIME
Low
Time from the front-panel TIME entry screen
FRONT PANEL DATE
Low
Time from the front-panel DATE entry screen
Summary of Contents for SEL-421-4
Page 6: ...This page intentionally left blank ...
Page 14: ...This page intentionally left blank ...
Page 30: ...This page intentionally left blank ...
Page 104: ...This page intentionally left blank ...
Page 128: ...This page intentionally left blank ...
Page 536: ...This page intentionally left blank ...
Page 584: ...This page intentionally left blank ...
Page 616: ...This page intentionally left blank ...
Page 696: ...This page intentionally left blank ...
Page 750: ...This page intentionally left blank ...
Page 755: ...Instruction Manual PM400 01 NB SEL 400 Series Relays Instruction Manual 20171006 ...
Page 776: ...This page intentionally left blank ...
Page 932: ...This page intentionally left blank ...
Page 976: ...This page intentionally left blank ...
Page 1024: ...This page intentionally left blank ...
Page 1038: ...This page intentionally left blank ...
Page 1064: ...This page intentionally left blank ...
Page 1128: ...This page intentionally left blank ...
Page 1206: ...This page intentionally left blank ...
Page 1316: ...This page intentionally left blank ...
Page 1350: ...This page intentionally left blank ...
Page 1464: ...This page intentionally left blank ...
Page 1468: ...This page intentionally left blank ...
Page 1492: ...This page intentionally left blank ...
Page 1518: ...This page intentionally left blank ...