Date Code 20020215
Factory-Set Logic
1-15
SEL-351R Instruction Manual
The note in Figure 1.11 refers to Figure 1.17—the logic that controls the High current trip -
phase (phase definite-time element 67P2T). In this example, High current trip - phase is enabled
for the third trip operation and every following trip operation.
The logic in Figure 1.8, Figure 1.9, Figure 1.10, Figure 1.12, Figure 1.13, and Figure 1.14
operates similarly to the High current trip - phase just discussed (Figure 1.11).
High Current Trip Operation When Reclosing Is Defeated
If reclosing is defeated via setting (e.g., all Operations to lockout
≤
1), then all the following
reclosing-related Relay Word bits default to logical 0 (the reclosing relay is nonexistent):
SH0, SH1, SH2, SH3, SH4
(shot counter states)
79RS, 79CY, 79LO
(reclosing relay states)
The logic at the top of Figure 1.11 and Figure 1.12 enables set phase and ground high current
trips, respectively, when reclosing is defeated.
DWG: M351R057
SH4
SH3
SH2
SH1
OLP
Relay
Word
bit
SH0
Relay
Word
bits
OPLKPH = 1
Operations to
lockout-phase
setting
OPLKPH = 2
OPLKPH = 3
OPLKPH = 4
OPLKPH = 5
Used in the following
SEL
OGIC
settings to
realize drive-to-
lockout conditions:
SV15
SV16
(see Figure 1.24)
Figure 1.8: Operations to Lockout - Phase Logic
Summary of Contents for SEL-351R
Page 12: ......
Page 14: ......
Page 18: ......
Page 74: ......
Page 76: ......
Page 82: ......
Page 136: ......
Page 140: ......
Page 176: ......
Page 180: ......
Page 332: ......
Page 334: ......
Page 460: ......
Page 466: ......
Page 476: ......
Page 478: ......
Page 510: ......
Page 512: ......
Page 522: ......
Page 548: ......
Page 550: ......
Page 576: ......
Page 610: ......
Page 616: ......