Date Code 20020215
Inputs, Outputs, Timers, and Other Control Logic
7-37
SEL-351R Instruction Manual
Traditional Indicating Panel Lights
Figure 7.28 shows traditional indicating panel lights wired in parallel with SEL-351R
optoisolated inputs. Input IN101 provides circuit breaker status to the relay, and input IN102
enables/disables reclosing in the relay via the following SEL
OGIC
control equation settings:
52A =
IN101
79DTL = !IN102
[= NOT(IN102); drive-to-lockout setting]
Figure 7.28: Traditional Panel Light Installations
Note that Figure 7.28 corresponds to Figure 7.2 (settings example).
Reclosing Relay Status Indication
In Figure 7.28, the 79 ENABLED panel light illuminates when the “79 Enable” switch is closed.
When the “79 Enable” switch is open, the 79 ENABLED panel light extinguishes, and it is
understood that the reclosing relay is disabled.
Circuit Breaker Status Indication
In Figure 7.28, the BREAKER CLOSED panel light illuminates when the 52a circuit breaker
auxiliary contact is closed. When the 52a circuit breaker auxiliary contact is open, the
BREAKER CLOSED panel light extinguishes, and it is understood that the breaker is open.
Traditional Indicating Panel Lights Replaced With Rotating Default Display
The indicating panel lights are not needed if the rotating default display feature in the SEL-351R
is used. Figure 7.29 shows the elimination of the indicating panel lights by using the rotating
default display.
Summary of Contents for SEL-351R
Page 12: ......
Page 14: ......
Page 18: ......
Page 74: ......
Page 76: ......
Page 82: ......
Page 136: ......
Page 140: ......
Page 176: ......
Page 180: ......
Page 332: ......
Page 334: ......
Page 460: ......
Page 466: ......
Page 476: ......
Page 478: ......
Page 510: ......
Page 512: ......
Page 522: ......
Page 548: ......
Page 550: ......
Page 576: ......
Page 610: ......
Page 616: ......