7-10
Inputs, Outputs, Timers, and Other Control Logic
Date Code 20020215
SEL-351R Instruction Manual
If settings are changed for a setting group other than the active setting group, there is no
interruption of the local bits (the relay is not momentarily disabled).
If a local control switch is made inoperable because of a settings change (i.e., the corresponding
label settings are nulled), the corresponding local bit is then fixed at logical 0, regardless of the
local bit state before the settings change. If a local control switch is made newly operable
because of a settings change (i.e., the corresponding label settings are set), the corresponding
local bit starts out at logical 0.
R
EMOTE
C
ONTROL
S
WITCHES
Remote control switches are operated via the serial communications port only (see
CON
Command (Control Remote Bit)
in
Section 10: Serial Port Communications and Commands
).
Figure 7.9: Remote Control Switches Drive Remote Bits RB1 Through RB8 (RB1
Through RB16 for the SEL-351R-2)
The outputs of the remote control switches in Figure 7.9 are Relay Word bits RBn called remote
bits, where n = 1 through 8 (1 through 16 for the SEL-351R-2), Use these remote bits in
SEL
OGIC
control equations.
Any given remote control switch can be put in one of the following three positions:
ON (logical
1)
OFF (logical
0)
MOMENTARY
(logical 1 for one processing interval)
Summary of Contents for SEL-351R
Page 12: ......
Page 14: ......
Page 18: ......
Page 74: ......
Page 76: ......
Page 82: ......
Page 136: ......
Page 140: ......
Page 176: ......
Page 180: ......
Page 332: ......
Page 334: ......
Page 460: ......
Page 466: ......
Page 476: ......
Page 478: ......
Page 510: ......
Page 512: ......
Page 522: ......
Page 548: ......
Page 550: ......
Page 576: ......
Page 610: ......
Page 616: ......