Standard Event Reports, Sag/Swell/Interruption Report, and SER
SEL-351 Instruction Manual
12-1
SECTION 12: STANDARD EVENT REPORTS, SAG/SWELL/
INTERRUPTION REPORT, AND SER
I
NTRODUCTION
The SEL-351 Relay offers two styles of event reports:
•
Standard 15/30-cycle event reports.
•
Sequential events recorder (SER) report.
Resolution:
1 ms
Accuracy:
+1/4 cycle
These event reports contain date, time, current, voltage, frequency, relay element, optoisolated
input, output contact, and fault location information.
The relay generates (triggers) standard 15/30-cycle event reports by fixed and programmable
conditions. These reports show information for 15 or 30 continuous cycles. The relay stores the
most recent event report data in nonvolatile memory. See Table 12.1 for the minimum number of
events stored, which depends on the LER setting (see the following subsection), and the firmware
version of the relay (see Table 1.2). If the event memory is full and more reports are triggered, the
latest event report overwrites the oldest event report. See Figure 12.2 for an example standard 15-
cycle event report.
Table 12.1: Minimum Event Report Capacity in Nonvolatile Memory
Firmware Version
LER = 15 Cycles
LER = 30 Cycles
0, 1, or 2
30
15
3 or 4
14
7
The relay adds lines in the sequential events recorder (SER) report for a change of state of a
programmable condition. The SER lists date and time-stamped lines of information each time a
programmed condition changes state. The relay stores the latest 512 lines of the SER report in
nonvolatile memory. If the report fills up, newer rows overwrite the oldest rows in the report. See
Figure 12.5 for an example SER report.
S
TANDARD
15/30-C
YCLE
E
VENT
R
EPORTS
See Figure 12.2 for an example event report (
Note
: Figure 12.2 is on multiple pages).
Event Report Length (Settings LER and PRE)
The SEL-351 Relay provides user-programmable event report length and prefault length. Event
report length is either 15 or 30 cycles. Prefault length ranges from 1 to 29 cycles. Prefault length
is the first part of the event report that precedes the event report triggering point.
Summary of Contents for SEL-351
Page 14: ...Courtesy of NationalSwitchgear com ...
Page 16: ...Courtesy of NationalSwitchgear com ...
Page 40: ...Courtesy of NationalSwitchgear com ...
Page 74: ...Courtesy of NationalSwitchgear com ...
Page 146: ...Courtesy of NationalSwitchgear com ...
Page 186: ...Courtesy of NationalSwitchgear com ...
Page 220: ...Courtesy of NationalSwitchgear com ...
Page 304: ...Courtesy of NationalSwitchgear com ...
Page 340: ...Courtesy of NationalSwitchgear com ...
Page 380: ...Courtesy of NationalSwitchgear com ...
Page 450: ...Courtesy of NationalSwitchgear com ...
Page 506: ...Courtesy of NationalSwitchgear com ...
Page 528: ...Courtesy of NationalSwitchgear com ...
Page 534: ...Courtesy of NationalSwitchgear com ...
Page 536: ...Courtesy of NationalSwitchgear com ...
Page 550: ...Courtesy of NationalSwitchgear com ...
Page 562: ...Courtesy of NationalSwitchgear com ...
Page 570: ...Courtesy of NationalSwitchgear com ...
Page 584: ...Courtesy of NationalSwitchgear com ...
Page 602: ...Courtesy of NationalSwitchgear com ...