APPENDIX F: SPECIAL APPLICATION SETTINGS
Some settings have special values to actuate line specific features. These are documented in this
appendix.
V
ALUE OF
“S”
FOR
E51N, E51Q
With typical settings of “Y” or “N”, the time overcurrent accumulation is blocked for a single-
pole open (SPO) condition. When E51N is set to “S”, SPO does not block the 51N elements.
When E51Q is set to “S”, SPO does not block the 51Q elements.
V
ALUE OF
“N1”
OR
“Y1”
FOR
ESPT S
ETTING
N1 activates special Scheme 1 Trip Logic if the SPTE contact enables single-pole tripping.
Y1 activates special Scheme 1 Trip Logic equations:
Figure F.1: Scheme 1 Trip Decision Logic for Phase A