K.5
Date Code 20060320
Instruction Manual
SEL-311C Relay
Unsolicited Fast SER Protocol
Functions and Function Codes
02-Function Code:
Disable Unsolicited
Data Transfer, Sent
From Master to Relay
This function disables the SEL-311C from transferring Fast SER data. The
message format for function code 02 is shown in
The SEL-311C verifies the message by checking the header, length, function
code, and disabled function code against the expected values, and checks the
entire message against the CRC-16 field. If any of the checks fail, except the
function code or the function to disable, the message is ignored.
If an acknowledge is requested as indicated by the least significant bit of the
status byte, the relay transmits an acknowledge message with the same
response number received in the enable message.
If the function to disable is not 18 or the function code is not recognized, the
relay responds with an acknowledge message containing the response code 01
(function code unrecognized) and no functions are disabled.
18-Function:
Unsolicited Fast SER
Response, Sent From
Relay to Master
The function 18 is used for the transmission of unsolicited Sequential Events
Recorder (Fast SER) data from theSEL-311C. This function code is also
passed as data in the “Enable Unsolicited Data Transfer” and the “Disable
Unsolicited Data Transfer” messages to indicate which type of Fast SER data
should be enabled or disabled. The message format for function code 18 is
shown in
Table K.2
Message Format for Function Code 02
Data
Description
A546
Message header
10
Message length (16 decimal)
0000000000
Five bytes reserved for future use as a routing address.
YY
Status byte (LSB = 1 indicates an acknowledge is requested)
02
Function code
C0
Sequence byte (Always C0. Other values
are reserved for future use in multiple frame messages.)
XX
Response number (XX = 00, 01, 02, 03, 01, 02...)
18
Function to disable (18 = Unsolicited Fast SER)
00
Reserved for future use as function code data
cccc
Two byte CRC-16 check code for message
Table K.3
Message Format for Function Code 18
(Sheet 1 of 2)
Data
Description
A546
Message header
ZZ
Message length (Up to 34 + 4 •
nn
decimal, where
nn
is the
maximum number of SER records allowed per message as
indicated in the “Enable Unsolicited Data Transfer” message.)
0000000000
Five bytes reserved for future use as a routing address.
YY
Status Byte
01 = need acknowledgment;
03 = settings changed and need acknowledgment.
If YY=03, the master should re-read the
SNS
data
because the element index list may have changed.
18
Function code
C0
Sequence byte (Always C0. Other values are
reserved for future use in multiple frame messages.)
Summary of Contents for SEL-311C
Page 1: ...20060320 SEL 311C Relay Protection and Automation System Instruction Manual PM311C 01 NB ...
Page 22: ...This page intentionally left blank ...
Page 42: ...This page intentionally left blank ...
Page 68: ...This page intentionally left blank ...
Page 128: ...This page intentionally left blank ...
Page 294: ...This page intentionally left blank ...
Page 330: ...This page intentionally left blank ...
Page 402: ...This page intentionally left blank ...
Page 406: ...This page intentionally left blank ...
Page 454: ...This page intentionally left blank ...
Page 574: ...This page intentionally left blank ...
Page 592: ...This page intentionally left blank ...
Page 616: ...This page intentionally left blank ...
Page 648: ...This page intentionally left blank ...
Page 652: ...This page intentionally left blank ...
Page 678: ...This page intentionally left blank ...
Page 682: ...This page intentionally left blank ...
Page 722: ...This page intentionally left blank ...
Page 724: ...This page intentionally left blank ...