Table 7.9: Zone 1 Phase-Ground Test Quantities at MTA ±45°
Angle IA
MTA +45°
-125.1°
MTA -45°
-35.1°
8.
Test the relay at the two additional current phase angle settings (MTA +45°,
MTA -45°). Record the results.
DIRECTIONAL ELEMENT TESTS
Verify the operate and restrain boundaries of the negative-sequence directional
element.
Method: Program the desired programmable output (A1 - A4) to follow the 32Q bit in Relay
Word row 1. Use the SET command to disable the LOP scheme. This prevents
test-condition voltages from setting the loss-of-potential condition and defeating the
directional sensing ability of the relay.
Purpose:
1.
Apply the following voltages to the relay:
Table 7.10: 32Q Test Voltages
VA
VB
VC
30.00
0.00
0.00
0.0°
0.0°
0 . 0 °
Volts
Degrees
For the voltages shown in Table 7.10, the resulting negative-sequence voltage is
ten volts. The following equations illustrate the equations you should use to
calculate magnitude and angle of V2.
7-28
Maintenance & Testing
SEL-221F, -1 Instruction Manual
Date Code 920508
Summary of Contents for SEL-221F
Page 3: ......
Page 10: ......
Page 11: ......
Page 12: ......
Page 13: ......
Page 69: ...Date Code 920508 Specifications SEL 221F 1 Instruction Manual 2 44 ...
Page 70: ...Date Code 920508 Specifications SEL 221F 1 Instruction Manual 2 45 ...
Page 71: ...Date Code 920508 Specifications SEL 221F 1 Instruction Manual 2 46 ...
Page 72: ...Date Code 920508 Specifications SEL 221F 1 Instruction Manual 2 47 ...
Page 110: ...Example Event Report 2 4 12 Event Reporting SEL 221F 1 Instruction Manual Date Code 930830 ...
Page 158: ...SETTINGS SHEET FOR SEL 221F RELAY PAGE 2 OF 6 DATE Date Code 921110 ...
Page 160: ...SETTINGS SHEET PAGE 4 OF 6 FOR SEL 221F RELAY DATE Date Code 930601 ...
Page 161: ...SETTINGS SHEET PAGE 5 OF 6 FOR SEL 221F RELAY DATE Date Code 961208 ...
Page 229: ...SEL 200 Series Relay Main Board Troubleshooting Test Points and Jumper Locations ...