If the air supply outlet of a ventilation system is
below
the blades, a minimum distance of 1
times the fan diameter from the blade tip is sufficient.
If the air supply outlet of a ventilation system is located
above
the blades, a minimum
distance of 2 times the fan diameter from the blade tip is necessary.
4.3
Required Installation Environment
Installation Environment
Conditions
Installation Location
Inside
Temperature Range
-15 + 55 °C
Please do not use the product in environments with strong
temperature fluctuations.
The product must not be exposed to frost.
Humiditiy
Below 95% relative humidity
Surrounding
The fan and controller must not be exposed to flammable or
corrosive gases. Metal powder, oils, water and other foreign
objects must not get into the controller.
Distances to hot springs e.g. heaters must be maintained. Please
note the manufacturer's safety clearances.
If MonsterFans are located in closed rooms with heaters with
indirect flue gas systems (unflued), parallel operation must be
prevented by interlocking it.