EN
55
Electrical connection
Notice
Connection of the appliance to the
power supply must be carried out by a
specialised electrician.
When the machine is operated for the
first time the
Data
and
Time
settings
are to be checked and if necessary, set
correctly (see
Settings / Menu Set-
tings
in the operating instructions).
Perform the electrical connection ac-
cording to the regulations or provisions
made by the local electricity authority
and utility companies.
In rooms in which fault-current protec-
tive switches are required or recom-
mended in order to increase safety, the
release current must be 30 mA.
►
Use a fault-current protective switch
with the
symbol.
Approval for fixed connection, all-pole
disconnectable by a main switch with
contact distance of min. 3 mm or plug
contact.
Warning
Risk of electric shock and risk of fire!
No extension cables, no multi-coupling
and no plug-in, mobile time switches
may be used.
The dryer may not be connected via an
external switching mechanism, which
regularly switches the machine on and
off (e. g. timer switch).
Reduced mains power
The appliance may be changed-over to
a reduced connection rate (see the fol-
lowing electrical installation schemes).
Additional information regarding
change-over capabilities are located on
the sticker on the power cable of the
machine.
Notice
The switchover must be carried out by a
specialist elec tri cian.
►
For lower connected loads, the setting
Reduced mains power
needs to be
adjusted accordingly.