4
B_LSDH_5340199
** Footnote:
According to IEC 60947-4-1, the types of protection mean:
”Assignment type 1”: Short circuits can cause damage to the contactors making replacement of the equipment necessary.
”Assignment type 2”: Easily separable contact welding but no other damage.
LSDH6... LSDH8...
AC 630 A AC 820 A
-220V
hp
200
290
-230V
hp
250
350
-460V
hp
500
700
-575V
hp
660
860
Break all lines
Suitable for use on a circuit capable of delivering not more than 42,000 rms
symmetrical amperes, 600 V max.
LSDH6...
LSDH8...
Short-circuit protection to
Fuse Links Duty class
IEC 60947-4-1**
gG
- Assignment type 1
A
1250
1250
- Assignment type 2
A
500
630
Auxiliary circuit
Rated operational current I
e
/AC-11
5,6 A at AC 230 V
Short-circuit protection:
- Fuse links
NEOZED and DIAZED
gG,16 A
- Circuit breaker
C, 10 A
B, 16 A
CIRCUIT
PROTECTIVE
DEVICE
(IF USED)
L1
L2
L3
FUSE
M
M
M
OLR
OLR
OLR
T1
T2
T3
3
PHASE
M OTOR
FUSE
FUSE
X1
H4
X2
H1
PRI.
SEC.
M
STOP
(1)
START
44
(2)
43
(3)
95
96
M
A1
A2
2 WIRE CONTROL (IF USED)
OLR
IF
CP
T
IS
US
E
D