B

YPASS  DISTRIBUTION  PANEL  AND  ACCESSORY 

USSDHOTSW8

 

INSTALLATION

 

 

 

ATTENTION: the installation must be performed by qualified personnel only. 

 
 

 

 

Example image 

(distribution panel for three phases installation)

 

NOTE 1: The  SWIN  and  SWOUT  (and  SWBYP)  switches  are  not 

mandatory  but  recommended,  as  the  wiring  connector  is 
protected from direct contact. 

NOTE 2: It is suggested that the mains cables enter from the upper side 

of the panel. Fit the cables to exit towards the UPS and the load 
on the lower side of the panel. 

NOTE 3: Upstream  of  the  distribution  panel  input  line,  install  the 

protection device prescribed in the UPS user manual 

NOTE 4: For  sizing  of  the  minimum  section  of  the  cables,  refer  to  the 

UPS user manual. 

NOTE 5: The switches used must have a current capacity greater than 

the nominal current of the UPS connected. 

 
 
 
 

WIRING DIAGRAM for single phase installation

 

 

 

 

DISTRIBUTION PANEL DIAGRAM 

INDICATIONS ON THE KIT 

CABLES YSDUE17…

 

 

 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

L_FUSE 
N_IN 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 

SW_BYP 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

SW_BYP 

 

 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

L_OUT 
N_OUT 

 
 
 
 
 
 
 
 
 
 

EARTH

 

 

 
 

 

 

MAINS 

LOAD 

TO UPS 

NOTE:  insulate 
the unused wires 
with a clamp 

Summary of Contents for GENIO Dual Power Series

Page 1: ...MANUAL Hotswap Kit Models USSDHOTSW4 USSDHOTSW8 Series GENIO Dual Power USSD...

Page 2: ...d or foreign bodies fall into the device The device must be used exclusively for the purpose for which it was designed Any other use is to be considered improper and as such dangerous The manufacturer...

Page 3: ...S SDU 8 10 KVA 5 CONNECTION PROCEDURE FOR SEPARATED BYPASS LINE UPS USSD 10000 DI 6 CONNECTION PROCEDURE FOR THREE PHASE UPS USSD 8 10 KVA TM 7 CLOSING THE TERMINALS DRAWER 7 MAINTENANCE BYPASS DISTRI...

Page 4: ...side of the UPS is protected by safety panels which should not be removed by untrained personnel All installation and maintenance or operations involving access inside the UPS require the use of tools...

Page 5: ...2 if present remove the pre installed jumper Model 4kVA Model 5 6kVA CONNECTION PROCEDURE FOR SINGLE PHASE UPS USSD 8 10 KVA Make the electrical connection of the new terminal cover drawer as shown i...

Page 6: ...move the jumper between the terminals JP and LBYPASS on the UPS terminals INPUT Connect the ground wire yellow green to the input ground terminal Connect the neutral wire marked N_IN blue to the NINPU...

Page 7: ...llow green to the input ground terminal Connect the neutral wire marked N_IN blue to the NINPUT terminal Connect the phase wire marked L_FUSE brown to the L1INPUT terminal Connect the phase wire marke...

Page 8: ...al NOTE 5 The switches used must have a current capacity greater than the nominal current of the UPS connected WIRING DIAGRAM DISTRIBUTION PANEL DIAGRAM INDICATIONS ON THE KIT CABLES YSDUE03 L_IN N_IN...

Page 9: ...of the panel Fit the cables to exit towards the UPS and the load on the lower side of the panel NOTE 3 Upstream of the distribution panel input line install the protection device prescribed in the UPS...

Page 10: ...o the auxiliary contact of the SERVICE BYPASS switch When the SERVICE BYPASS switch closes this auxiliary contact opens indicating to the UPS that the SERVICE BYPASS has been inserted If this connecti...

Page 11: ...et are designed in such a way as not to allow connection errors Fixing example Model 5 6 kVA Finally lock the plug to the socket using the special retaining hook as shown in the figure below Fixing ex...

Page 12: ...le the SWMB switch is open OFF position SERVICE BYPASS MANAGE TO DISCONNECT THE UPS 1 Close the SWMB switch SERVICE BYPASS 2 Turn off the UPS refer to the UPS user manual 3 Open the SWIN and SWOUT swi...

Page 13: ...TSW8 version SINGLE PHASE CONFIGURATION THREE PHASE CONFIGURATION STANDARD SEPARATED BYPASS LINE Input voltage V 220 240 1W N PE 380 415 3W N PE Input current A 50 18 for each phase Voltage on BYPASS...

Page 14: ...14 MAN_USSDHOTSW4_USSDHOTSW8_EN_2020_06_22_0MNSDUE0 32LIB docx 0MNSDUE032LIB...

Reviews: