background image

3

SRB301STV.2 /CCV.2 /PCV.2
SRB301STV.3 /CCV.3 /PCV.3

Operating instructions
Safety-monitoring module

EN

Outputs 

Number of safety contacts:

 3

Number of auxiliary contacts: 

1

Number of signalling outputs:  

0

Max. switching capacity of the safety contacts: 

13-14; 23-24; 33-34: 

max. 250 V, 8 A ohmic (inductive in case of  

suitable protective wiring); min. 10 V / 10 mA;  

residual current at ambient temperature  

up to 45°C: 24 A / 55°C: 18 A / 60°C: 12 A

Switching capacity of the auxiliary contacts:

 

41-42: 24 VDC / 2 A

Fuse rating of the  

 

safety contacts:

 

external (I

k

 = 1000 A) to EN 60947-5-1  

Safety fuse 10 A quick blow, 8 A slow blow

Fuse rating for the a 

 

uxiliary contacts: 

external (I

k

 = 1000 A) to EN 60947-5-1  

Safety fuse 2.5 A quick blow, 2 A slow blow

Utilisation category to EN 60947-5-1: 

AC-15: 230 VAC / 6 A  

DC-13: 24 VDC / 6 A

Dimensions H x W x D: 

 

- SRB301ST/PCV.2/V.3: 

 

100 x 22.5 x 121 mm; 

- SRB301STV.2/V.3: 

 

120 x 22.5 x 121 mm; 

- SRB301ST/CCV.2/V.3: 

 

130 x 22.5 x 121 mm

The data specified in this manual are applicable when the  

component is operated with rated operating voltage U

e

 ±0%.

2.5  Safety classification

Standards: 

EN ISO 13849-1, IEC 61508, EN 60947-5-1

PL: 

up to e

Control category: 

up to 4

DC: 

99% (high)

CCF: 

> 65 points

PFH value: 

≤ 2.00 × 10

-8

/h

SIL: 

up to 3

Service life: 

20 years

The PFH value of 2.00 × 10

-8

/h applies to the combinations of contact 

load (current through enabling contacts) and number of switching cy-
cles (n

op/y

) mentioned in the table below. At 365 operating days per year 

and a 24-hours operation, this results in the below-mentioned switching 
cycle times (t

cycle

) for the relay contacts.

Diverging applications upon request.

Contact load

n

op/y

t

cycle

20 %

525,600

1.0 min

40 %

210,240

2.5 min

60 %

75,087

7.0 min

80 %

30,918

17.0 min

100 %

12,223 

43.0 min

3.  Mounting

3.1  General mounting instructions

Mounting: snaps onto standard DIN rails to EN 60715.

Snap the bottom of the enclosure slightly tilted forwards in the DIN rail 
and push up until it latches in position.

3.2  Dimensions

All measurements in mm.

Device dimensions (H/W/D): 
SRB301ST/PCV.2/V.3:   100 x 22.5 x 121 mm
SRB301STV.2/V.3:  

120 x 22.5 x 121 mm

SRB301ST/CCV.2/V.3:   130 x 22.5 x 121 mm

4.  Electrical connection

4.1  General information for electrical connection

As far as the electrical safety is concerned, the protection 
against unintentional contact of the connected and therefore 
electrically interconnected apparatus and the insulation of the 
feed cables must be designed for the highest voltage, which 
can occur in the device.

The electrical connection may only be carried out by autho-
rised personnel in a de-energised condition.

Wiring examples: see appendix

To avoid EMC disturbances, the physical ambient and opera-
tional conditions at the place where the product is installed, 
must meet the provisions laid down in the paragraph "Electro-
magnetic Compatibility (EMC)" of DIN EN 60204-1.

5.  Operating principle and settings

5.1  Operating principle after the operating voltage is switched on

The safety-monitoring module checks whether the enabling contacts 
of the relay are opened. If the safety guard is closed and the exter-
nal reset button is actuated or an automatic start is programmed, the 
enabling paths of the safety-monitoring module will close. The cables 
and the connected safety switches are tested when the safety guards 
are opened. This check expects a signal change on both inputs of the 
switch when the safety guard is opened. If this change does not take 
place, the release is blocked, even when the "right" signals for this situ-
ation are measured at the inputs when the safety guard is closed again. 
When the safety guard is opened, the enabling paths of the safety-mon-
itoring module is opened as well.

5.2  LED functions

• K1: Status channel 1

• K2: Status channel 2

•  U

B

: Status operating voltage (LED is on, when the operating  

voltage on the terminals A1 - A2 is ON)

•  U

i

: Status internal operating voltage (LED is on, when the  

operating voltage on the terminals A1 - A2 is ON and the  
fuse has not been triggered).

•  QS: cross-wire short detection status (LED on when 

 

cross-wire short detection active)

5.3  Description of the terminals

Voltages:

A1

A2

+24 VDC/24 VAC

0 VDC/24 VAC

Inputs:

S11-S12

S21-S22

S21-S22

Input channel 1 (+)

Input channel 2 (+) (without cross-wire  

short detection)

Input channel 2 (–) (with cross-wire  

short detection)

Outputs:

13-14

23-24

33-34

41-42

First safety enabling circuit

Second safety enabling circuit

Third safety enabling circuit

Auxiliary NC contact as signalling contact

Start:

S12-X2

S12-X3

Feedback circuit and external reset (monitored)

Feedback circuit and automatic start

Summary of Contents for SRB301ST/PCV.2

Page 1: ...ust be exclusively used in accordance with the versions listed below or for the applications authorised by the manufacturer Detailed information regarding the range of applications can be found in the...

Page 2: ...11 S12 and or S21 S22 are opened The safety relevant current paths with the outputs contacts 13 14 23 24 and 33 34 meet the following requirements under observation of a PFH value assessment also refe...

Page 3: ...for electrical connection As far as the electrical safety is concerned the protection against unintentional contact of the connected and therefore electrically interconnected apparatus and the insulat...

Page 4: ...ch the components after electrical discharge Setting the switch see Fig 3 The cross wire short monitoring function factory setting is pro grammed by means of the switch underneath the front cover of t...

Page 5: ...reset button e g welded contacts or manipulations which could lead to an inadvertent restart are detected in this configuration and will result in an inhibition of the operation Automatic start see Fi...

Page 6: ...he control circuits are detected Cross wire shorts between the control circuits are not detected Category 3 PL e to DIN EN ISO 13849 1 possible Dual channel control of magnetic safety switches accordi...

Page 7: ...nt EC Directives 2006 42 EC EC Machinery Directive 2004 108 EC EMC Directive 1995 16 EG EC Lift Directive Person authorised for the compilation of the technical documentation Oliver Wacker M ddinghofe...

Page 8: ...A Schmersal GmbH Co KG M ddinghofe 30 D 42279 Wuppertal Postfach 24 02 63 D 42232 Wuppertal Phone 49 0 2 02 64 74 0 Telefax 49 0 2 02 64 74 1 00 E Mail info schmersal com Internet http www schmersal c...

Reviews: