background image

9

SRB-E-212ST / SRB-E-322ST

Operating instructions

Safety-monitoring module

EN

7.3  Start configuration

7.3.1 External reset button

•  Manual start or activation of the module occurs when the button  

is released (detection of the trailing edge).

Monitoring of max. actuation time 0.03 sec. … 3 sec.

If the time is exceeded, the module cannot be started!

7.3.2 Reset without monitoring / autostart

•  The manual start or the activation of the module occurs when the 

button is pressed (not when it is released!).

•  With autostart, X2 must be bridged to S11, S21 or +24 VDC

Not admitted without additional measure due to the risk of 

gaining access by stepping behind!

Within the meaning of EN 60204-1 paragraph 9.2.5.4.2, 

the operating mode "automatic start" is only restrictedly 

admissible. In particular, any inadvertent restart of the 

machine must be prevented by other suitable measures.

X2

J

S11/S21

X2

+24

 

VDC

J

Reset button (detection of the 

trailing edge)

Reset without monitoring / 

autostart

Rotary knob position 1

Rotary knob position 6

Rotary knob position 2

Rotary knob position 7

Rotary knob position 3

Rotary knob position 8

Rotary knob position 4

Rotary knob position 9

Rotary knob position 5

Rotary knob position 10

7.4  Feedback circuit / Release signal

•  Suitable for increase in capacity or number of contacts by means of 

contactors or relays with positive-guided contacts. If the feedback 

circuit is not required, establish a bridge.

X3

S11/S21

X3

+24

 

VDC

K

B

K

A

K

B

K

A

•  The safety contacts and outputs can be switched during operation via 

the safety input X7 with the guard system closed.

•  The safety outputs Qt1 and Qt2 are not switched off until the set delay 

time has elapsed.

•  For safety-orientated use, a fault in the wiring (short circuit to 24 V 

potential) must be able to be excluded!

•  If no deactivation during operation is required, this input must be 

switched to + 24 VDC.

X7

X7

+24

 

VDC

 = control signal

Summary of Contents for SRB-E-212ST

Page 1: ...ure to comply with this warning notice could lead to physical injury and or damage to the machine Content 1 About this document 1 1 Function 1 1 2 Target group authorised qualified personnel 1 1 3 Explanation of the symbols used 1 1 4 Appropriate use 2 1 5 General safety instructions 2 1 6 Warning about misuse 2 1 7 Exclusion of liability 2 2 Product description 2 1 Ordering code 2 2 2 Special ver...

Page 2: ...pt no liability for damages resulting from the use of unauthorised spare parts or accessories For safety reasons invasive work on the device as well as arbitrary repairs conversions and modifications to the device are strictly forbidden the manufacturer shall accept no liability for damages resulting from such invasive work arbitrary repairs conversions and or modifications to the device The safet...

Page 3: ...on category to IEC 60947 5 1 AC 15 230 V 4 A DC 13 24 V 4 A Switching capacity of the auxiliary contacts 41 42 24 VDC 1 A Fuse rating for the auxiliary contact safety fuse 2 5 A quick blow 2 A slow blow Safety contact values resistance max 100 mΩ AgNi self cleaning positive action Electrical life refer to 2 5 Mechanical life 10 million operations Semi conductor outputs Switching capacity of the sa...

Page 4: ... for the relay contacts Diverging applications upon request Contact load nop y tcycle 20 880 000 0 6 min 40 330 000 1 6 min 60 110 000 5 0 min 80 44 000 12 0 min 100 17 600 30 0 min 3 Mounting 3 1 General mounting instructions Mounting snaps onto standard DIN rails to EN 60715 Hook bottom of enclosure in DIN rail and push down until it engages in position 3 2 Dimensions All measurements in mm Devi...

Page 5: ...fety outputs STOP 0 Out 1 Outputs activated For flash code see section 5 4 Qt1 Qt2 Safety outputs STOP 1 Out 2 Outputs activated For flash code see section 5 4 1 0 S11 S12 S21 S22 A1 A2 X3 X2 X7 Qt1 Y2 Y1 SRB E 212ST 24 23 14 13 Out 2 time s RUN ERR ln 1 ln 2 Out 1 mode 1 0 S11 S12 S21 S22 A1 A2 X3 X2 Qt2 Qt1 X7 Y2 SRB E 322ST 24 23 14 13 42 41 34 33 time s RUN ERR ln 1 ln 2 Out 1 Out 2 mode Adjus...

Page 6: ...e Rotary mode switch Rotary time switch System response LED indications RUN In 1 In 2 Out Factory setting Position 1 0 s Ready for application 1 Switch operating voltage on Position 1 Without connected sensors Lights up Turn to position C Application 1 is deleted Lights up Flashes Flashes Flashes Setting cycle active Application 1 is deleted No valid application stored Flashes SRB E ready for new ...

Page 7: ...Continuously lit Not a valid application Flashes In 1 Input S12 closed Continuously lit Time window for synchronicity exceeded Flashes quickly Second channel input S22 has not opened Flashes slowly In 2 Input S22 closed Continuously lit Time window for synchronicity exceeded Flashes quickly Second channel input S12 has not opened Flashes slowly Out 1 Safety output STOP 0 ON Continuously lit No rel...

Page 8: ...1 23 13 33 41 24 14 34 42 K1 K2 L1 KA KB N KC KD a b c d e f Key a Safety inputs b Safety outputs c Signalling outputs d Clock outputs e Processing f Power 7 2 Application example Dual channel control shown for a guard door monitor with two position switches where one has a positive break contact with external reset button J Relay outputs Suitable for 2 channel control for increase in capacity or ...

Page 9: ...ther suitable measures X2 J S11 S21 X2 24VDC J Reset button detection of the trailing edge Reset without monitoring autostart Rotary knob position 1 Rotary knob position 6 Rotary knob position 2 Rotary knob position 7 Rotary knob position 3 Rotary knob position 8 Rotary knob position 4 Rotary knob position 9 Rotary knob position 5 Rotary knob position 10 7 4 Feedback circuit Release signal Suitabl...

Page 10: ...ng autostart 8 Set up and maintenance 8 1 Commissioning The safety relay module features protection class IP54 for installation in a switch cabinet The safety relay module is delivered ready for operation Application 1 is preset in the factory 8 2 Functional testing The safety function of the safety monitoring module must be tested The following conditions must be previously checked and met 1 Corr...

Page 11: ... must be replaced 9 Disassembly and disposal 9 1 Disassembly The safety monitoring module must be disassembled in a de energised condition only 9 2 Disposal The safety monitoring module must be disposed of in an appropriate manner in accordance with the national prescriptions and legislations 10 Appendix 10 1 Wiring circuit information Wiring example for cascading via safety input X7 Safety output...

Page 12: ...ny Internet www schmersal com We hereby certify that the hereafter described components both in their basic design and construction conform to the applicable European Directives Name of the component SRB E 212ST SRB E 322ST Type See ordering code Description of the component Relay safety combination for emergency stop circuits guard door monitoring solenoid safety switches and AOPDs Relevant Direc...

Reviews: