schmersal SRB 220XV2 V.2 Operating Instructions Manual Download Page 7

7

SRB 220XV2 V.2

Operating instructions

Safety-monitoring module

EN

8.4  Actuator configuration

Single-channel control with feedback circuit (Fig. 18)

•  Suitable for increase in capacity or number of contacts by means of 

contactors or relays with positive-guided contacts.

•  

S

 = feedback circuit:  

If the feedback circuit is not required, establish a bridge.

Dual-channel control with feedback circuit (Fig. 19)

•  Suitable for increase in capacity or number of contacts by means of 

contactors or relays with positive-guided contacts.

•  

S

 = feedback circuit:  

If the feedback circuit is not required, establish a bridge.

S33

S34

47

13

48

14

K

B

K

A

S

L1

N

K

A

K

C

S33

S34

47

13

48

14

K

B

K

C

K

D

K

A

K

B

L1

N

K

A

K

D

K

C

S

Fig. 18

Fig. 19

Differential control with feedback circuit (see Fig. 20)

•  Suitable for increase in capacity or number of contacts by means of 

contactors or relays with positive-guided contacts.

•  

S

 = feedback circuit:  

If the feedback circuit is not required, establish a bridge. If the  

enabling circuit of the controller must be equipped with its own  

feedback circuit, this circuit must be integrated as shown in the  

wiring example "dual-channel control with feedback circuit"  

(see there).

 

S33

S34

47

13

48

14

K

A

L1

N

K

A

S

a)

Fig. 20

a) Enabling signal controller

Summary of Contents for SRB 220XV2 V.2

Page 1: ...versions listed below or for the applications authorised by the manufacturer Detailed information regarding the range of applications can be found in the chapter Product description To avoid EMC dist...

Page 2: ...th the output contacts 13 14 and 23 24 meet the following requirements under observation of a B10D value assessment also refer to Requirements to DIN EN ISO 13849 1 control category 4 PL e to DIN EN I...

Page 3: ...results in the below mentioned switching cycle times tcycle for the relay contacts Diverging applications upon request Contact load nop y tcycle 20 525 600 1 0 min 40 210 240 2 5 min 60 75 087 7 0 min...

Page 4: ...saved in the SRB 220XV2 the voltage supply must be interrupted for approx 3 seconds ON ON SW1 SW2 1 1 2 2 3 3 4 4 Fig 3 New adjustable drop out delays and cross wire short monitoring for version V 2...

Page 5: ...iptions and legislations 8 Appendix 8 1 Wiring examples Dual channel control shown for a guard door monitor with two contacts A and B where at least one is a positive break contact with external reset...

Page 6: ...s between the control circuits are detected Control category 4 to EN 954 1 Category 4 PL e to DIN EN ISO 13849 1 possible Single channel guard door monitoring circuit with interlocking devices to EN 1...

Page 7: ...s S feedback circuit If the feedback circuit is not required establish a bridge S33 S34 47 13 48 14 KB KA S L1 N KA KC S33 S34 47 13 48 14 KB KC KD KA KB L1 N KA KD KC S Fig 18 Fig 19 Differential con...

Page 8: ...omponent SRB220XV2 V 2 Description of the component Safety monitoring module for emergency stop circuits and guard door monitoring Relevant Directives Machinery Directive EMC Directive RoHS Directive...

Reviews: