2
Operating instructions
Safety-monitoring module
EN
SRB 207AN/1-230V
1.6 Warning about misuse
In case of inadequate or improper use or manipulations of the
safety-monitoring module, personal hazards or damages to
machinery or plant components cannot be excluded.
The relevant requirements of the standard EN 1088 must be
observed.
1.7 Exclusion of liability
We shall accept no liability for damages and malfunctions resulting from
defective mounting or failure to comply with this operating instructions
manual. The manufacturer shall accept no liability for damages
resulting from the use of unauthorised spare parts or accessories.
For safety reasons, invasive work on the device as well as arbitrary
repairs, conversions and modifications to the device are strictly forbid
-
den; the manufacturer shall accept no liability for damages resulting
from such invasive work, arbitrary repairs, conversions and / or
modifications to the device.
2 Product description
2.1 Ordering code
This operating instructions manual applies to the following types:
SRB 207AN/1-230V
Only if the information described in this operating instructions
manual are realised correctly, the safety function and therefo-
re the compliance with the Machinery Directive is maintained.
2.2 Special versions
For special versions, which are not listed in the order code below 2.1,
these specifications apply accordingly, provided that they correspond to
the standard version.
2.3 Destination and use
The safety-monitoring module for integration in safety circuits is desig-
ned for fitting in control cabinets. It is used for the safe evaluation of the
signals of positive break position switches for safety functions or
magnetic safety sensors on sliding, hinged and removable safety
guards as well as emergency stop control devices.
Design
The safety-monitoring module has a multichannel structure. It includes
safety relays with monitored positive action contacts. The NO contacts
of the relays, which are wired in series, build the enabling contacts.
6 signalling outputs signal the position of the corresponding safety
guard.
2.4 Technical data
Standards:
IEC / EN 60204-1; EN 60947-5-1;
EN 60947-5-3; EN ISO 13849-1;
IEC 61508; BG-GS-ET-14;
BG-GS-ET-20
Start conditions:
automatic or start button
(optionally monitored)
Feedback circuit available:
yes
Start-up test:
no
Pull-in delay for automatic start:
typ. 120 ms
Pull-in delay with reset button:
typ. 30 ms
Drop-out delay in case of
emergency stop:
typ. 20 ms
Rated operating voltage Ue:
48 … 240 VAC
Rated insulation voltage U
i
:
250 V
Rated impulse withstand voltage
U
imp
:
4 kV
Thermal test current I
the
:
6 A
Internal electronic protection
(Y/N):
yes, tripping current > 1.0 A, reset
after approx. 1 second
Power consumption:
6,8 VA, plus signalling outputs
Y1-Y6, 32
Input monitoring:
Cross-wire short detection:
yes
Wire breakage detection:
yes
Earth leakage detection:
yes
Number of NC contacts:
6
Number of NO contacts:
6
Max. conduction resistance:
40 Ω
Outputs:
Stop category 0:
2
Stop category 1:
0
Number of safety contacts:
2
Number of auxiliary contacts:
0
Number of signalling outputs:
7
Switching capacity of the
signalling outputs:
32, Y1-Y6: 24 VDC (intern) / 20
mA, residual current max. 40 mA
Fuse rating of the signalling
outputs:
Internal electronic fuse
Max. switching capacity of the
safety contacts:
250 VAC, 6 A ohmic (inductive
incase of appropriate protective
wiring)
Utilisation category to
EN 60947-5-1:
AC-15: 250 V / 6 A
DC-13: 24 V / 6 A
Max. fuse rating:
6 A gG D-fuse
Mechanical life:
10 million operations
LED indication:
3
Ambient conditions:
Operating temperature:
-25 °C ... +45 °C
Storage and transport
temperature:
-25 °C ... +70 °C
Protection class:
Enclosure: IP40
Terminals: IP20
Wiring compartment: IP54
Degree of pollution:
2
Fixing:
Snaps onto standard DIN rails to
DIN EN 60715
Connection type:
Plug-in screw connection
Min. cable section:
0.25 mm²
Max. cable section:
2.5 mm², rigid or flexible
Weight:
400 g
Dimensions (H/W/D):
100 × 45 × 121 mm
The data specified in this manual is applicable when the component is
operated with rated operating voltage
Ue ±0%.