Operating instructions

Safety light curtain/safety light grid

SLC440AS

SLG440AS

EN

TRANSMITTER LED

Status LED

Description

Transmitting

On

Standard operation, transmitter active

flashing

Configuration error

Information

flashing

Beam coding A is active

6.2  Fault diagnostic

The light grid performs an internal self-test after the operating voltage is switched on and the protection field is enabled When a fault is detected, an 

error number eg E2 is displayed at the receiver Each fault display is followed by a one-second delay

Status display Fault feature

Action

Supply voltage U-Aux

U-Aux = 24 VDC+/- 10%, check voltage source and primary voltage, note: after the 

fault message E2 has been displayed three times, a reset is executed 

Errors at the internal OSSD outputs

Internal error:
Short-circuit or cross-wire short at internal OSSD

Beam blanking

Check the blanking area(s) of fixed or floating objects with the selected parameter 
setting, fault elimination - repeat configuration in the parameter setting, possibly 
adjust P 1, P 2, P 3

Configuration error in parameter setting

Check parameter setting and save/accept with "S" delete/clear with "C"

System error

Restart the system, if E 7 display persists, exchange components

The error display is reset after elimination of the error cause and after the receiver has been switched back on

The error indication displays a 3-digit system error code for every 10th display

6.3  AS-i diagnostics indication

The AS-i LED indications in the end cap on the connecting side have 

the following meaning (to EN 50295):

AS-i LED  

(Duo-LED)

Meaning

Green

AS-i data transmission

Red

No data transmission or slave address = 0

Alternate flashing 

green / red

Internal device error / periphery error (FID) 

detected

6.4  Read-out of the parameter ports

The parameter port P0 to P3 of an AS-i slave can be read out through 

the control interface of the AS-i master (see component description) by 

using the "Write parameter" instruction (with hexadecimal value F) This 

(non-safe) diagnostic information from the reflected parameters or the 

answer to a "Write parameter instruction" can be used by the user for 

diagnostic purposes or for the control programme

Diagnostic information P0 … P3

Parameter bit

Condition = 1

P0

-

P1

Poor beam quality

P2

-

P3

Internal device error detected (FID)

The warning message indicates a soiled or incorrectly adjusted BWS

The warning message indicates a soiled or incorrectly adjusted AOPD

6.5  Diagnostic signal periphery error (FID)

An internal device error is transmitted as "periphery error" to the control 

system through the AS-i Master

A "periphery error" (FID input of the AS-i chip) is signaled by the 

alternating red and green flashing of the AS-i duo LED on the AS-i 

device

7.  Set-up and maintenance

7.1  Check before start-up

Prior to start-up, the following items must be checked by the 

responsible person 

Wiring check prior to start-up:

1  For the auxiliary voltage supply, a 24 VDC PELV unit must be used 

(refer to technical data) 

A power downtime of 20 ms must be bridged

2  Presence of a voltage supply with correct polarity at the SLC/SLG 

3  The connecting cable of the transmitter is correctly connected to the 

transmitter and the connecting cable of the receiver correctly to the 

receiver

4  If two or more SLC/SLG units are used within close range to each 

other, an alternating arrangement must be observedAny mutual 

interference of the systems must be prevented

Switch the SLC/SLG on and check the operation in the following 

way:

The component performs a system test during approx 2 seconds 

after the operating voltage has been switched on (indication through 

7-segment display)  After that, the outputs are enabled, if the protection 

field is not interrupted  The LED "OSSD ON" at the receiver is on

In case of incorrect functionality, please follow the instructions 

listed in the chapter Fault diagnostic

Summary of Contents for SLC440AS

Page 1: ...authorised qualified personnel 1 1 3 Explanation of the symbols used 1 1 4 Appropriate use 2 1 5 General safety instructions 2 1 6 Warning about misuse 2 1 7 Exclusion of liability 2 2 Product descri...

Page 2: ...re strictly forbidden the manufacturer shall accept no liability for damages resulting from such invasive work arbitrary repairs conversions and or modifications to the device 2 Product description 2...

Page 3: ...AS i device insulation internal short circuit proof AS i specification Version V 3 0 Profile S 0 B F E AS i inputs Channel 1 Data bits DI 0 DI 1 dynamic code transmission Channel 2 Data bits DI 2 DI 3...

Page 4: ...ction field areas Systems with alternative beam coding A can be ordered through the type code refer to type code 2 8 1 Fixed blanking SLC440AS The SLC440AS can blank stationary objects in the protecti...

Page 5: ...ncreases the resolution In this way the physical resolution changes into an effective resolution This effective resolution must be used to calculate the safety distance Use formula 1 to calculate the...

Page 6: ...oding A must be ordered separately for each sensor transmitter and receiver 2 11 Parameter setting The parameter setting of the SLG440AS enables the individual adjustment of the desired functionality...

Page 7: ...ed as preventive warning notices to ensure a safe and appropriate handling These guidelines are an essential part of the safety instructions and therefore must always be observed and respected The SLC...

Page 8: ...permanently displayed on the receiver when the safety enabling is switched on For the optical representation of the signal quality two ranges the signal strength at the 2nd and the last beam in the p...

Page 9: ...he safety guard relays etc d Resolution of the safety light curtain The approach speed is covered with a value of 2000 mm s If value S 500 mm after the calculation of the safety distance then use this...

Page 10: ...faces must be taken into account In case of an incorrect installation interruptions of the protection field could possibly not be detected which could lead to serious injuries The hereafter specified...

Page 11: ...730 XX 730 844 863 SLC440AS ER 0810 XX 810 924 943 SLC440AS ER 0890 XX 890 1004 1023 SLC440AS ER 0970 XX 970 1084 1103 SLC440AS ER 1050 XX 1050 1164 1183 SLC440AS ER 1130 XX 1130 1244 1263 SLC440AS ER...

Page 12: ...atus display Switching condition Optional accessories Centre support MS 1110 Mounting kit consists of 2 steel angles and 4 spacers for central fixing 4 27 8 11 5 19 5 11 5 54 3 69 38 5 5 3 27 3 7 Inte...

Page 13: ...ol system through the AS i master To thiseffect the 4 input bits with the varying SaW code of a Safety at Work slave are evaluated through an OR operation with 4 inputs in the control system 6 Diagnos...

Page 14: ...read out through the control interface of the AS i master see component description by using the Write parameter instruction with hexadecimal value F This non safe diagnostic information from the refl...

Page 15: ...middle between the transmitter and the receiver 3 No hazardous machine movement when the test rod is within the protection field 4 The hazardous machine movement comes to standstill when the voltage...

Page 16: ...13166201 Person authorized for the compilation of the technical documentation Oliver Wacker M ddinghofe 30 42279 Wuppertal The currently valid declaration of conformity can be downloaded from the inte...

Reviews: