SLC 220 IP 69 K

SLG 220 IP 69 K

Operating instructions

Safety light curtain / safety light grid

2.8  Functions

The system consists of a receiver and a transmitter. For the described 

functions, no further switching elements are required. For the diag-

nostics and function selection, a user-friendly PC-software is offered as 

accessory. For the connection to a PC, the NSR-0700 BUS converter is 

required (not included in delivery).

The system has the following features:

•  Protective mode (automatic start after release of the protected field)

•  Start interlock

•  Restart interlock (manual reset)

•  Contactor control EDM

•  Blanking of fixed protection field areas

Factory setting

The SLC/SLG 220 system features many functions without additional 

devices. The following table gives an overview of the possible functions 

and the factory settings configuration.

Function

Factory set-

ting

Configuration

Protective mode

not active

External wiring

Restart interlock 
(manual reset)

active

External wiring

Fixed blanking

not active

With BUS converter
NSR-0700 and PC-software

Contactor control

not active

With BUS converter
NSR-0700 and PC-software

Start interlock

not active

With BUS converter
NSR-0700 and PC-software

Switch-on delay

not active

With BUS converter
NSR-0700 and PC-software

2.8.1 Protective mode

The protective mode switches the OSSD outputs to ON state (protec-

tion field not interrupted), without external release of a switching device. 

This type of protection generates an automatic restart of the machine if 

the protection field is not interrupted.

This operating mode may only be chosen in conjunction with 

the restart interlock of the machine. This operating mode 

must not be chosen, when persons can step behind the 

protection field.

2.8.2 Restart interlock (manual reset)

The restart interlock prevents an automatic enabling of the outputs 

(OSSD's ON state) after switch-on of the operating voltage or an inter-

ruption of the protection field.

Restart interlock (manual reset) active (factory setting)

The SLC/SLB 220 series only switches to the ON state, when a 

command device is connected to the restart interlock input. To enable 

the outputs, the command device must be actuated no longer than 2.5 

seconds.

Deactivating the restart interlock (manual reset)

Wire the restart interlock input (PIN 1) of the transmitter to the signal 

quality output (PIN 1) of the receiver.

The command devices (enabling button) must be installed 

outside of the hazardous area. The operator must have a 

clear view on the hazardous area when actuating the enab-

ling button.

2.8.3 Fixed blanking

The SLC 220 can blank stationary parts in the protection field.

Multiple protection field areas can be blanked.

Fixed blanking area

E1

R1

The range of the fixed blanking can be arbitrarily chosen in the protec-

tion field. Multiple areas can be blanked. At least one light beam must 

be active in the protection field.

The area of the fixed blanking must not be modified after 

the teach-in process. Any change of the area or removal of 

the part from the protection field will result in the absence of 

monitoring in certain areas of the protection field. After every 

shifting (part(s) in the protection field), a new teach-in process 

must be executed.

• The remaining lateral areas must be protected against intru-

sion by means of mechanical covers.

• The lateral covers must be fixed with the object. Partial 

covers are not authorised.

• After the fixed blanking, the protection field must be tested 

by means of the test rod.

• The restart interlock function of the safety light curtain or the 

machine must be activated.

•  The standard IEC/TS 62046 includes information, which 

describes possibly required additional measures to prevent 

a person from reaching a hazard through the blanking areas 

of a protection field.

•  After configuration, the protection field must be checked by 

a responsible person by means of a test rod; in addition to 

that, this person must compare the size of the blanked area 

to the object size and if necessary provide for additional 

covers or a larger distance of the safety guard with regard to 

the hazardous point.

The function is activated by means of the NSR-0700 BUS 

converter and a PC or laptop. The activation of the function 

is signaled by the LED blanking flashing in the diagnostic 

window of the transmitter.

The light beams of the SLG 220 series cannot be blanked.

2.8.4 Contactor control EDM (feedback)

The contactor control monitors the controlled switching elements 

(auxiliary contacts of the contactors) of both outputs. This monitoring 

is realised after each interruption of the protection field and prior to 

the restart (enabling) of the outputs. In this way, malfunctions of the 

relays are detected, e.g. contact welding or contact spring breakage. 

If the light curtain detects a malfunction of the switching elements, the 

outputs are locked. After fault rectification, the operating voltage must 

be once switched off and back on (power reset).

The contactor control is not activated upon delivery. This 

function is activated by means of the NSR-0700 BUS conver-

ter and a PC or laptop.

Summary of Contents for SLC 220 IP 69 K

Page 1: ...ymbols used Information hint note This symbol is used for identifying useful additional informa tion Caution Failure to comply with this warning notice could lead to failures or malfunctions Warning Failure to comply with this warning notice could lead to physical injury and or damage to the machine 1 4 Appropriate use The products described in these operating instructions are developed to execute...

Page 2: ...ld heights in mm available lengths 0175 0250 0325 0475 0625 0775 0925 1075 1225 1375 1525 1675 30 80 Resolution 30 80 mm Range 0 3 m 6 m H Range 4 m 14 m high range only for resolution 30 mm SLG 220 E R 69 RF No Option Description Distance between outermost beams 0500 02 500 mm 2 beam 0800 03 800 mm 3 beam 0900 04 900 mm 4 beam Range 0 3 m 6 m H Range 5 m 30 m high range Only if the information de...

Page 3: ...IGH 11 120 mA Input current LOW 0 2 mA Function SLC 220 Protective mode start and restart interlock contactor control fixed beam blanking SLG 220 start and restart interlock contactor control Signal times Contactor control 20 300 ms Restart interlock manual reset 20 ms 1 0 s signal trans mission in case of trailing edge Start interlock 250 1500 ms adjustable LED indications transmitter Transmittin...

Page 4: ...he hazardous area The operator must have a clear view on the hazardous area when actuating the enab ling button 2 8 3 Fixed blanking The SLC 220 can blank stationary parts in the protection field Multiple protection field areas can be blanked Fixed blanking area E1 R1 The range of the fixed blanking can be arbitrarily chosen in the protec tion field Multiple areas can be blanked At least one light...

Page 5: ... series must be activated refer to wiring diagram 4 1 The max test time of 150 ms must be observed to the standard EN 61496 3 Mounting 3 1 General conditions The following guidelines are provided as preventive warning notices to ensure a safe and appropriate handling These guidelines are an essential part of the safety instructions and therefore must always be observed and respected The SLC SLG mu...

Page 6: ...d Approach speed Resolution of the safety light curtain Safety light curtain SLC 220 The safety distance for resolutions 14 mm up to 40 mm is calculated by means of the following formula S 2000 mm s T 8 d 14 mm S Safety distance mm T Total reaction time machine stopping time reaction time of the safety guard relays etc d Resolution of the safety light curtain The approach speed is covered with a v...

Page 7: ...the EN 999 for calculating the minimum distances of the safety guards with regard to the hazardous point are EN ISO 13855 and EN ISO 13857 The safety distance between the safety light grid and the hazardous point must always be respected and observed If a person reaches the hazardous point before the hazardous movement has come to standstill he she is exposed to seri ous injuries 3 4 1 Minimum dis...

Page 8: ...1429 1477 1513 SLC 220 E R1525 xx 69 RFB 1525 1579 1627 1663 SLC 220 E R1675 xx 69 RFB 1675 1729 1777 1813 All versions with resolution 30 and 80 mm as well as variant H range from 4 0 to 14 0 m have identical dimensions with the same protection field height For the SLC 220 E R0175 30 69 RFB type the dimension changes from 23 mm to 35 5 mm due to the extended profile length The protec tion field i...

Page 9: ...9 EN SLC 220 IP 69 K SLG 220 IP 69 K Operating instructions Safety light curtain safety light grid Accessories Fixing kit MS 1035 14 5 42 18 9 20 6 5 40 32 52 ...

Page 10: ... outputs OSSD 1 OSSD 2 kn1 kn2 Auxiliary contacts of the last switching relay for contactor control optional S1 Command device for external test optional S2 Command device for restart interlock manual reset enabling E1 Power supply 24 VDC 10 RS 485 A B These connections between the transmitter and the receiver are required for the operation 4 2 Connector configuration Receiver Emitter possibly acc...

Page 11: ...ns please make sure that the user has the necessary information at his disposal to be able conducting the maintenance 5 3 Regular check A regular visual inspection and functional test including the following steps is recommended 1 The component does not have any visible damages 2 The optics cover is not scratched or soiled 3 Hazardous machinery parts can only be accessed by passing through the pro...

Page 12: ...ture Action OSSD OFF and LED re start continuous flashing If the function contactor control is activated and no state change has been detected at the contactor control input after enabling of the OSSD Check contactor control connection Check the connected contactor for closed contact if OSSD ON contactor control input must show GND level if OSSD OFF contactor control input must show 24V Switch on ...

Page 13: ...mode is automatically realised after Power Reset when the BUS converter is no longer integrated and the connecting cable of the sensor is reconnected 7 Disassembly and disposal 7 1 Disassembly The safety switchgear must be disassembled in a de energised condi tion only 7 2 Disposal The safety switchgear must be disposed of in an appropriate manner in accordance with the national prescriptions and ...

Page 14: ...entation Ulrich Loss Möddinghofe 30 42279 Wuppertal Notiied body for the prototype test TÜV Nord Cert GmbH Langemarckstr 20 45141 Essen ID n 0044 EC prototype test certiicate n 44 205 10 555867 004 Safety Control GmbH Am Industriepark 33 D 84453 Mühldorf Inn Telefon 49 0 86 31 187 9 60 Telefax 49 0 86 31 187 9 61 E Mail info safetycontrol com Place and date of issue Wuppertal February 1 2010 Autho...

Reviews: