7
SEPK 02.0 / SEPG 05.3 / SEP 01.0 /
SEP 01.4 / SEPLC 05.2 / SEP 07.0 / SEP 09.0
Operating instructions
Two-hand control panel
EN
Switching points:
NC contact: typ.1 mm
NO contact: typ.2.5 mm
Mounting position:
any
Mechanical life:
10 × 10
6
operations
Actuating force at stroke
end:
typ. 4.5 N
Connection:
Screw terminals
Cable section:
solid wire: 2 × (2 … 2 mm
2
)
stranded wire (with conductor ferrules):
2 × (2 … 2 mm
2
)
Tightening torque:
Connecting screw: max. 1 Nm
Shock-protection:
available (save illuminated element
individually mounted)
Approvals:
cULus (under preparation)
3.5 Technical data ADP... pushbutton
Standards:
IEC 947, EN IEC 60947, DIN VDE 0660,
DIN EN 50007, DIN EN 60068
Installation diameter:
22.3 mm
Front plate area:
1 … 6 mm
Connection:
Knurled nut, central mounting
Max. tightening torque:
1 Nm
Mounting position:
any
Temperature range:
–25 °C … +60 °C
Climate resistance:
to DIN EN 60068 Part 2-30
Protection class:
IP 65
Sealing type:
Lip gaskets, lat gaskets
Fully insulated:
Yes
Materials:
PA GV
Front ring execution:
PA GV
3.6 Technical data RF contact elements for ADP...
Standards:
EN IEC 60947, DIN VDE 0660,
DIN EN 60664, DIN EN 60068
Rated operating voltage
U
e
max.:
400 V
Utilisation category:
AC-13, DC-15
Operating current I
e
:
depending on the utilisation category and
the test voltage:
8 A: AC-15, 250 VAC
5 A: DC-13, 24 VDC
Thermal nominal current
Ith (in air):
10 A
Max. fuse rating:
gG 10 A
Air clearances and creepa-
ge distances
4 kV/3
Evidence of the positive
break:
2.5 kV impulse voltage
Positive break travel:
typ. approx. 2 mm after the opening point
Switching of low voltages
min. 24 VDC / 5 mA
Switching frequency to:
1,200 s/h
Temperature range:
–25°C … +60°C
Climate resistance:
Part 2-30
Mounting position:
any
Mechanical life:
10 × 10
5
operations
Switch travel:
typ.3.5 mm
Resistance to shock:
30 g / 16 ms
Resistance to vibrations:
20 g / 10 … 150 Hz
Wiring coniguration:
to EN 60947
Actuating force at stroke
end:
typ. 9 N
Switching points:
NC contact: typ.1 mm
NO contact: typ.2.5 mm
Enclosure material:
PA GV self-extinguishing, hardly lam-
mable
Connection:
Screw terminals
Cable section:
solid wire: 2 × (2 … 2 mm
2
)
stranded wire with conductor ferrules:
2 × (2 … 2 mm
2
)
Tightening torque:
Connecting screw max. 1 Nm
Rated insulation voltage U
i
: for degree of pollution 3: 400 V
Protection class:
Connections: IP 20 (inger-safe)
Switching elements: IP 40
Protection against acciden-
tal contact with live parts:
available (to EN 50 274 and BGV A2)
Approvals:
cULus
3.7 Technical data emergency stop command devices EDRR…,
KDRR…, ADR…, EDRZ… (Elan)
ED EFR + EF303.1 Command device, red colour,
mounting diameter 22.3 mm, head
diameter: 38.5 mm, 1 NO + 1 NC
ED EFR + EF303.1 Command device, red colour, moun-
ting diameter 1 mm, head diameter:
1 mm, 1 NO + 1 NC
KDR EFR +
EF303.1
Command device, red colour,
mounting diameter 22.3 mm, head
diameter: 38.5 mm, 1 NO + 1 NC
RF10 + RF03
Command device, red colour,
mounting diameter 22.3 mm, head
diameter: 40 mm, 1 NO + 1 NC
ED EF303.1
Command device, red colour, moun-
ting diameter 1 mm, head diameter:
1 mm, 1 NO + 1 NC
EF033.1 + EF220.1
Switching elements, 2 NO + 2 NC (in
separated form)
EF303.1 + EF303.2
Switching elements, 2 NO + 2 NC
(for emergency stop)
RF10 + RF10 + RF03 + RF03 Switching elements, 2 NO + 2 NC
(for A-programme emergency stop
with maximum equipment)
3.8 Technical data of the EDRR... emergency stop command device
Standards
IEC 60947-5-1, IEC 60947-5-5,
IEC 60947-1, EN ISO 13850
Design
round
Mounting
∅
22.3 mm
Spacing
for head Ø 40 mm: 50 × 40 mm,
for head Ø 50 mm: 50 × 50 mm
Front plate thickness
1 … 6 mm
Mounting position
any
Climate resistance to DIN
EN 60068
Part 2-30
Ambient temperature
–25 °C … +75 °C
Protection class to
IEC 605290
IP65
Fully insulated
yes
Material mushroom button Al anodised
Fixing
with mounting lange
Max. tightening torque for
the ELM ixing screws
0.6 Nm
Actuating force
approx. 25 N
Mechanical life
1 × 10
5
operations
Rohs compliant:
yes
Contact elements
Standards
IEC/EN 60947-5-1
Rated operating voltage
U
e
max.:
400 V
Rated insulation voltage U
i
for degree of pollution 3 to
EN 60 947-1:
400 V
Rated impulse withstand
voltage U
imp
:
4 kV
Thermal nominal current
I
th
(in air):
10 A