7.  Set-up and maintenance

7.1  Functional testing

The safety function of the safety components must be tested. The 

following conditions must be previously checked and met:

1. Fitting of the sensor and the actuator.

2. Fitting and integrity of the power cable.

3.  The system is free of dirt and soiling (in particular metal chips).

7.2  Maintenance

In the case of correct installation and adequate use, the safety 

switchgear features maintenance-free functionality.

A regular visual inspection and functional test, including the following 

steps, is recommended:

1. Check the safety function

2. Check the fixing and integrity of the safety switchgear, the actuator 

and the cable

3. Remove possible metal chips.

Adequate measures must be taken to ensure protection 

against tampering, either to prevent tampering of the safety 

guard, for instance by means of replacement actuators. 

Damaged or defective components must be replaced.

8.  Disassembly and disposal

8.1  Disassembly

The safety switchgear must be disassembled in a de-energised 

condition only.

8.2  Disposal

The safety switchgear must be disposed of in an appropriate manner in 

accordance with the national prescriptions and legislations.

Summary of Contents for RSS36-ST-AS

Page 1: ...rding the range of applications can be found in the chapter Product description 1 5 General safety instructions The user must observe the safety instructions in this operating instructions manual labe...

Page 2: ...ition for as long as the safety guard is open The safety switchgears are classified according to ISO 14119 as type 4 switching devices Designs with individual coding are classified as highly coded and...

Page 3: ...de brouillage et 2 l utilisateur de l appareil doit accepter tout brouillage radio lectrique subi m me si le brouillage est susceptible d en compromettre le fonctionnement 2 6 Safety classification S...

Page 4: ...2 sao 10 10 sar 20 20 With the combination of old sensor new actuator V2 there may be limitations in availability owing to the reduced sao 8 mm This change has no affect on the performance level The s...

Page 5: ...following teach in procedure 1 Switch the safety sensor s voltage supply off and back on 2 Introduce the actuator in the detection range The teach in procedure is signalled at the safety sensor yellow...

Page 6: ...green flashing Off 1 static 0 Internal device error periphery error red green flashing Flashes 1 1 static 0 AS i error slave address 0 or communication error red depending on the condition 0 static 0...

Page 7: ...lar visual inspection and functional test including the following steps is recommended 1 Check the safety function 2 Check the fixing and integrity of the safety switchgear the actuator and the cable...

Page 8: ...ption of the component Non contact safety sensor with integrated AS i Safety at Work Relevant Directives 2006 42 EC 2014 53 EU 2011 65 EU Machinery Directive RED Directive RoHS Directive Applied stand...

Reviews: