background image

3

EN

FWS 1206

Operating instructions

Fail-safe standstill monitor 

2.5 

Safety classification

Standards:

EN ISO 13849-1; IEC 61508

PL:

up to d

Control category:

up to 3

PFH value:

1.0 x 10

-7

 / h; applicable for 

applications with up to max.  

50,000 switching cycles / year and 

max. 80 % contact load. Diverging 

applications upon request.

SIL:

up to 2

Service life:

20 years

3  Mounting

3.1  General mounting instructions

Mounting: snaps onto standard DIN rails to EN 60715.

3.2  Dimensions

Device dimensions (H/W/D): 100 x 22.5 x 121 mm

4  Electrical connection

4.1  General information for electrical connection

The electrical connection may only be carried out by 

 authorised personnel in a de-energised condition.

Wiring examples: see appendix

5  Operating principle and settings

Operating principle after the operating voltage is switched on

After the operating voltage is switched on, the initialisation is started. 

After verification, the inputs of the fail-safe standstill monitor are 

 evaluated. The cyclic frequencies of the connected proximity switches 

are compared to programmed limit frequencies.

To check the proximity switches, a second comparison between the 

signal of the safety contact and the detected frequency is executed. If 

the value drops below the programmed frequency and the contact of 

the contactor indicates a standstill of the motor (contact closed), both 

safety relays are actuated and the enabling paths are closed. If one of 

the standstill conditions no longer is fulfilled (frequency or condition of 

the contactor), the safety relays are disabled.

When the motor is started through the contactor, the function of the 

proximity switches is tested. Five seconds after the contactor start-up, 

the programmed limit frequency must be exceeded at the cyclic inputs. 

If not, the fail-safe standstill monitor signals an error. Error messages 

cause the safety relays to be disabled.

When two proximity switches are connected

If the programmed upper or lower limit frequency is exceeded, the fre-

quencies of both proximity switches are compared. A divergence of over 

30% will be considered faulty and signalled. The yellow LED is flashing 

(refer to ISD table).

Inputs X1-X4

X1: connection for proximity switch 1

X2: connection for proximity switch 2 or bridge to X1

X3:  connection for reset button  

The reset input has a double function  

A rising flank (0/1) at X3 deletes all detected errors of the fail-safe 

standstill monitor and causes the relays to be disabled. A static 

High signal (closed contact) changes the function of output Y2. 

Instead of a simple error message, the impulse sequence is  

emitted for every detected error in accordance with the "Error 

indication" table.

X4: connection for an additional standstill signal "high": standstill

Outputs

Enabling paths 13/14, 23/24

NO contacts for safety function

Additional outputs Y1/Y2

Y1: Authorized operation; the enabling path is closed

Y2:  "error“ or impulse sequence to "Error indication" table

Note

The additional outputs Y1 and Y2 must not be integrated in the safety 

circuit. If only one proximity switch is connected, the inputs X1 and X2 

must be bridged.

6  Set-up and maintenance

6.1  Functional testing

The safety function of the safety-monitoring module must be tested. 

The following conditions must be previously checked and met:

1. Proper fitting of the safety-monitoring module

2. Fitting and integrity of the power cable

6.2  Maintenance

In the case of correct installation and adequate use, the safety-monitor-

ing module features maintenance-free functionality. 

A regular visual inspection and functional test, including the following 

steps, is recommended:

• Check the correct fixing of the safety monitoring module

• Check the cable for damage.

Damaged or defective components must be replaced.

7  Disassembly and disposal

7.1  Disassembly

The safety monitoring module must be disassembled in the de-ener-

gised condition only.

7.2  Disposal

The safety monitoring module must be disposed of in an appropriate 

manner in accordance with the national prescriptions and legislations.

Summary of Contents for FWS 1206

Page 1: ...o execute safety related functions as part of an entire plant or machine It is the responsibility of the manufacturer of a machine or plant to ensure the proper functionality of the entire machinery or plant The safety monitoring module must be exclusively used in accordance with the versions listed below or for the applications authorised by the manufacturer Detailed information regarding the ran...

Page 2: ...The fail safe standstill monitor has a dual channel redundant structure It is provided with two safety relays with monitored positive guided contacts which are controlled by two independent microprocessors The NO contacts of the series wired relays build the enabling paths The feed cables of both proximity switches power supply must be laid so that in case of a wire breakage only one proximity swi...

Page 3: ... connected If the programmed upper or lower limit frequency is exceeded the fre quencies of both proximity switches are compared A divergence of over 30 will be considered faulty and signalled The yellow LED is flashing refer to ISD table Inputs X1 X4 X1 connection for proximity switch 1 X2 connection for proximity switch 2 or bridge to X1 X3 connection for reset button The reset input has a doubl...

Page 4: ...switch connection cables in areas where strong interference signals are present e g frequency converters or cable leads from powerful electric motors the utilisation of shielded cables may be necessary Legend A B Safety switch S Feedback circuit X Additional standstill signal I 0 On off switch H Start button E Unlocking button J Reset button A1 A2 14 13 21 22 41 42 51 52 71 72 63 64 AZM161 12 12 F...

Page 5: ...oximity switch Only one proximity switch bridge X1 X2 is missing 4 impulses Interference at inputs no safe evaluation Too high capacitive or inductive interference at the inputs or the supply voltage lead 5 impulses One or both relays did not close within the monitoring time Too low operating voltage Ue Defective relay 6 impulses Relay not disabled upon the actuation of the switch May be due to co...

Page 6: ...ate of issue Wuppertal October 7 2009 Authorised signature Heinz Schmersal Managing Director Name of the safety component type FWS 1206 Description of the safety component Fail safe standstill monitor Harmonised EC Directives 2006 42 EC EC Machinery Directive 2004 108 EC EMC Directive Person authorized for the compilation of the technical documentation Ulrich Loss Möddinghofe 30 42279 Wuppertal No...

Reviews: