3

AZM 170 I

Operating instructions

Solenoid interlock

EN

2.4  Technical data

Standards:

 

IEC 60947-5-1, ISO 14119, BG-GS-ET-19

Enclosure:

 

glass-fibre reinforced thermo- 

plastic, self-extinguishing

Actuator and locking bolt:

 

stainless steel 1.4301

Contact material:

 Silver

Holding force F:

 

1000 N

Latching force: 

5 N  

- Ordering suffix R:

 

30 N

Coding level according to ISO 14119: 

high

Protection class:

 IP67

Contact type:

 

change-over contact with double break, type Zb  

or 2 NC contacts, with galvanically  

separated contact bridges

Switching system:

 

A

 IEC 60947-5-1; slow action,  

NC contact with positive break

Cable entry:

 

M20 x 1.5

Connection:

 

Cut clamps, screw terminals or M12 connector

Cable type:

 flexible

Cable section:  

 

- IDC method of termination (cut clamps): 

 

0.75...1.0 mm² 

- Screw terminals: 

 

0.25...1.5 mm² (incl. insulated 

conductor ferrules)

Rated impulse withstand voltage U

imp

:

 

4 kV  

- Connector:

 

0.8 kV

Rated insulation voltage U

i

:

 

250 V  

- Connector:

 

60 V

Thermal test current I

the

:

 

6 A  

- Connector:

 

2 A

Utilisation category:

 

DC 13  

- AZM 170-…-11 and AZM 170-…-02 

 

AC-15, DC-13  

- Connector:

 DC-13

Rated operating current/voltage I

e

/U

e

:

 

4 A / 24 VDC;  

4 A / 230 VAC;  

- Connector:

 

2 A / 24 VDC

Required short-circuit current:

 

1000 A

Max. fuse rating:

 

6 A gG D-fuse

Connector: 

 

2 A gG D-fuse

Positive break travel:

 

11 mm

Positive break force:

 

8.5 N for each NC contact fitted

Magnet:

 

100% ED

Rated control voltage U

s

:

 

24 VAC / DC;  

110 VAC 50 / 60 Hz;  

230 VAC 50 / 60 Hz

Power consumption:

 

max. 12 W

Ambient temperature:

 

−25 °C … +60 °C

Mechanical life:

 

> 1 million operations

Actuating speed:

 

max. 2 m/s

Actuating frequency:

 

max. 1000 operations/h

2.5  Safety classification

Standards: 

ISO 13849-1

Envisaged structure: 

 

- Basically: 

applicable up to Cat. 1 / PL c

 

-  With 2-channel usage and  

 

fault exclusion mechanism*: 

applicable up to Cat. 3 / PL d  

with suitable logic unit

B

10d

 NC contact: 

2,000,000

B

10d

 NO contact at 10% ohmic contact load: 

1,000,000

Service life: 

20 years

* If a fault exclusion to the 1-channel mechanics is authorised.

MTTF

B

d x

x

h

s/h

3600

d

10d

op

op

op

n

0,1 x n

op

t

cycle

(Determined values can vary depending on the application-specific 

parameters h

op

, d

op

 and t

cycle

 as well as the load.)

If multiple safety components are wired in series, the Performance 

Level to ISO 13849-1 will be reduced due to the restricted error 

detection under certain circumstances.

3.  Mounting

3.1  General mounting instructions

On delivery, the actuator is in inserted condition. For  

power-to-unlock components, the actuator must be released 

by means of the manual release. If the triangular key is 

turned 180°, the locking bolt is pulled into the unlocking 

position. The normal locking function is only restored after 

the triangular key has been returned to its original position.

Two mounting holes are provided for fixing the enclosure. The solenoid 

interlock is double insulated. The use of an earth wire is not authorised. 

The solenoid interlock must not be used as an end stop.  Any mounting 

position. The mounting position must be chosen so as to avoid the 

penetration of dirt in the used holes. The unused opening must be 

sealed by means of slot sealing plugs. Tightening force for the Torx T10 

cover screws 0.7 ...  1 Nm.

The safety component and the actuator must be permanently 

fitted to the safety guards and protected against displacement 

by suitable measures (tamperproof screws, gluing, drilling, 

pinning).

Please observe the relevant requirements of the standards 

ISO 12100, ISO 14119 and ISO 14120.

Summary of Contents for AZM 170 series

Page 1: ...sions listed below or for the applications authorised by the manufacturer Detailed information regarding the range of applications can be found in the chapter Product description 1 5 General safety instructions The user must observe the safety instructions in this operating instructions manual the country specific installation standards as well as all prevailing safety regulations and accident pre...

Page 2: ...ith the Machinery Directive is maintained 2 2 Special versions For special versions which are not listed in the order code below 2 1 these specifications apply accordingly provided that they correspond to the standard version 2 3 Destination and use The solenoid interlock has been designed to prevent in conjunction with the control part of a machine movable safety guards from being opened before h...

Page 3: ...ISO 13849 1 Envisaged structure Basically applicable up to Cat 1 PL c With 2 channel usage and fault exclusion mechanism applicable up to Cat 3 PL d with suitable logic unit B10d NC contact 2 000 000 B10d NO contact at 10 ohmic contact load 1 000 000 Service life 20 years If a fault exclusion to the 1 channel mechanics is authorised MTTF B d x x h s h 3600 d 10d op op op n 0 1 x nop t cycle Determ...

Page 4: ... ordering suffix 2197 AZM 170 ST with connectors 2 x 4 poles A or B coding ø 4 2 24 22 15 20 M12 M12 37 90 18 31 4 60 17 15 5 23 8 2 AZM 170ST with connectors 1x 4 poles 1 x 8 poles ø 4 2 24 22 15 58 18 16 16 90 18 31 4 76 5 17 16 23 8 2 18 Actuator Straight actuator B1 Angled actuator B5 30 22 20 23 2 33 10 4 3 4 5 30 22 20 8 23 12 2 36 13 7 5 4 3 Flexible actuator B6L Flexible actuator B6R 22 32...

Page 5: ...r B6L B6R b a a b b a a b b a a b The B6L or B6R actuators are set to the smallest radius in factory To increase the radius the setting screws a b must be turned by means of a hexagonal key A F 2 5 mm 4 Electrical connection 4 1 General information for electrical connection The electrical connection may only be carried out by authorised personnel in a de energised condition If the risk analysis in...

Page 6: ...5 6 7 8 13 11 12 14 1 NO 1 NC 2 NC ordering suffix 11 02 1 NO 1 NC 2 NC ordering suffix 11 02 11 13 14 12 A1 41 31 32 42 A2 31 41 42 32 A1 A2 1 2 3 4 13 11 12 14 1 2 3 4 5 6 7 8 31 41 42 32 A1 A2 1 2 3 4 13 11 12 14 1 2 3 4 5 6 7 8 A1 11 13 14 12 41 31 32 42 A2 AZM 170 I with connector Power to unlock Power to lock 1 NO 1 NC ordering suffix 11 1 NO 1 NC ordering suffix 11 A1 A2 14 22 21 32 13 1 1 ...

Page 7: ...k and the actuator 2 Check the integrity of the cable entry and connections 3 Check the switch enclosure for damage 5 2 Maintenance A regular visual inspection and functional test including the following steps is recommended 1 Check for tight installation of the actuator and the switch 2 Remove particles of dust and soiling 3 Check cable entry and connections Adequate measures must be taken to ens...

Page 8: ... 14119 2014 Person authorized for the compilation of the technical documentation Oliver Wacker Möddinghofe 30 42279 Wuppertal K A Schmersal GmbH Co KG Möddinghofe 30 D 42279 Wuppertal Postfach 24 02 63 D 42232 Wuppertal Phone 49 0 2 02 64 74 0 Telefax 49 0 2 02 64 74 1 00 E Mail info schmersal com Internet http www schmersal com Place and date of issue Wuppertal September 7 2016 Authorised signatu...

Reviews: