3
AZM 170 I
Operating instructions
Solenoid interlock
EN
2.4 Technical data
Standards:
IEC 60947-5-1, ISO 14119, BG-GS-ET-19
Enclosure:
glass-fibre reinforced thermo-
plastic, self-extinguishing
Actuator and locking bolt:
stainless steel 1.4301
Contact material:
Silver
Holding force F:
1000 N
Latching force:
5 N
- Ordering suffix R:
30 N
Coding level according to ISO 14119:
high
Protection class:
IP67
Contact type:
change-over contact with double break, type Zb
or 2 NC contacts, with galvanically
separated contact bridges
Switching system:
A
IEC 60947-5-1; slow action,
NC contact with positive break
Cable entry:
M20 x 1.5
Connection:
Cut clamps, screw terminals or M12 connector
Cable type:
flexible
Cable section:
- IDC method of termination (cut clamps):
0.75...1.0 mm²
- Screw terminals:
0.25...1.5 mm² (incl. insulated
conductor ferrules)
Rated impulse withstand voltage U
imp
:
4 kV
- Connector:
0.8 kV
Rated insulation voltage U
i
:
250 V
- Connector:
60 V
Thermal test current I
the
:
6 A
- Connector:
2 A
Utilisation category:
DC 13
- AZM 170-…-11 and AZM 170-…-02
AC-15, DC-13
- Connector:
DC-13
Rated operating current/voltage I
e
/U
e
:
4 A / 24 VDC;
4 A / 230 VAC;
- Connector:
2 A / 24 VDC
Required short-circuit current:
1000 A
Max. fuse rating:
6 A gG D-fuse
Connector:
2 A gG D-fuse
Positive break travel:
11 mm
Positive break force:
8.5 N for each NC contact fitted
Magnet:
100% ED
Rated control voltage U
s
:
24 VAC / DC;
110 VAC 50 / 60 Hz;
230 VAC 50 / 60 Hz
Power consumption:
max. 12 W
Ambient temperature:
−25 °C … +60 °C
Mechanical life:
> 1 million operations
Actuating speed:
max. 2 m/s
Actuating frequency:
max. 1000 operations/h
2.5 Safety classification
Standards:
ISO 13849-1
Envisaged structure:
- Basically:
applicable up to Cat. 1 / PL c
- With 2-channel usage and
fault exclusion mechanism*:
applicable up to Cat. 3 / PL d
with suitable logic unit
B
10d
NC contact:
2,000,000
B
10d
NO contact at 10% ohmic contact load:
1,000,000
Service life:
20 years
* If a fault exclusion to the 1-channel mechanics is authorised.
MTTF
B
d x
x
h
s/h
3600
d
10d
op
op
op
n
0,1 x n
op
t
cycle
(Determined values can vary depending on the application-specific
parameters h
op
, d
op
and t
cycle
as well as the load.)
If multiple safety components are wired in series, the Performance
Level to ISO 13849-1 will be reduced due to the restricted error
detection under certain circumstances.
3. Mounting
3.1 General mounting instructions
On delivery, the actuator is in inserted condition. For
power-to-unlock components, the actuator must be released
by means of the manual release. If the triangular key is
turned 180°, the locking bolt is pulled into the unlocking
position. The normal locking function is only restored after
the triangular key has been returned to its original position.
Two mounting holes are provided for fixing the enclosure. The solenoid
interlock is double insulated. The use of an earth wire is not authorised.
The solenoid interlock must not be used as an end stop. Any mounting
position. The mounting position must be chosen so as to avoid the
penetration of dirt in the used holes. The unused opening must be
sealed by means of slot sealing plugs. Tightening force for the Torx T10
cover screws 0.7 ... 1 Nm.
The safety component and the actuator must be permanently
fitted to the safety guards and protected against displacement
by suitable measures (tamperproof screws, gluing, drilling,
pinning).
Please observe the relevant requirements of the standards
ISO 12100, ISO 14119 and ISO 14120.