AZM 170 AS
Operating instructions
Solenoid interlock
EN
Diagnostic information:
Green LED:
Red LED:
Yellow LED:
AS-Interface supply voltage
AS-Interface communication error or
slave address = 0
Enabling status
Input module address:
preset to address 0, can be changed
through AS-interface bus master or
hand-held programming device
Auxiliary voltage magnet:
Operating voltage range:
24 VDC - 15% /+10% (stabilised PELV)
Power consumption AUX:
max. 0.5 A
Rated insulation voltage
Ui2:
32 VDC
Rated impulse withstand
voltage Uimp2:
800 V
Device fuse rating:
≤ 4 A when used to UL 508
Magnet:
100% ED
Ambient conditions:
Ambient temperature:
-25 °C ... +55 °C
Storage and transport
temperature:
-25 °C ... +85 °C
Relative humidity:
30...95%, no condensation
Resistance to vibration:
10 ... 150 Hz, amplitude 0.35 mm
Resistance to shock:
30 g / 11 m/s
Switching frequency f:
≤ 1 Hz
Switch-off delay:
< 100 m/s
Actuating speed:
≤ 2 m/s
2.5 Safety classiication
Standards:
EN ISO 13849-1, IEC/EN 61508
If a fault exclusion of a hazardous damage to the 1-channel me-
chanics is authorised and suficient protection against tampering is
ensured
PL:
up to d
Control category:
up to 3
PFH value:
1.01 x 10
-7
/ h
for ≤ 100,000 operations / year
SIL:
up to 2
Service life:
20 years
Basically suitable up to:
PL:
up to c
Control category:
up to 1
PFH value:
1.14 x 10
-6
/ h
for ≤ 100,000 operations / year
SIL:
up to 1
Service life:
20 years
3 Mounting
3.1 General mounting instructions
Two mounting holes are provided for ixing the enclosure. The solenoid
interlock is double insulated. The use of a protective ground wire
therefore is not authorised. The solenoid interlock must not be used
as an end stop. Any mounting position may be used provided that the
ingression of dirt in the used opening is avoided. The unused opening
must be sealed by means of slot sealing plugs. Tightening force for the
Torx T10 cover screws 0.7 ... 1 Nm
Please observe the remarks of the standards EN ISO 12100,
EN 953 and EN 1088.
Mounting of the actuator
See mounting instructions actuators
3.2 Dimensions
All measurements in mm.
ø
4,2
22
15
90
31
60
23
8
30
30
8
37
M12
4 Electrical connection
4.1 General information for electrical connection
The electrical connection may only be carried out by authorised
personnel in a de-energised condition.
The AZM 170 AS solenoid interlock is supplied through the AS-Interface
system. The energy for the locking magnet is individually supplied
(AUX). Both voltage supplies of the solenoid interlock must be equipped
with a protection against permanent overvoltage. To that effect, stabi-
lised PELV supply units must be used.
The connection to the AS-Interface system is realised through an M12
connector. The M12 connector is A-coded. The wiring coniguration of
the M12 connector is deined as follows (to EN 50295):
AUX +(P)
3
2
1
4
AS-Interface -
AS-Int
AUX -(P)
5 Functions and coniguration
5.1 Mode of operation of the safety outputs
AZM 170 B ST-AS
The safety outputs of the AS-i safety monitor are enabled, when the
following condition is met:
• the actuator is inserted
AZM 170 BZ ST-AS
The safety outputs of the AS-i safety monitor are only activated, when
both AS-i half-codes are enabled.
Half-code 1
(AS-i SaW bit 0,1) is enabled, when:
• the solenoid interlock is locked
The solenoid interlock now can be locked.
Half-code 2
(AS-i SaW bit 2,3) is enabled, when:
• the actuator is inserted