5 / 6
no function – menu skip
Using the menu 6 „mode“
Switching characteristic „up-range“ – „normally closed“
state
output
switch 1
normal
state
output
switch 2
(optional)
setpoint 1
normal
green
green
red
red
setpoint 2
„Up-range“: the normal range is above setpoint 1 and setpoint 2
First of all the user has to define the device normal range. For example:
- The device should indicate (green LED) if the pressure is under the setpoints, mode
„down-range“ has to be selected. With other words: the measure value is normally
under the setpoints.
- The device should indicate (green LED) if the pressure is over the setpoints, mode
„up-range“ has to be selected. (The measure value is normally over the setpoints.)
- The device should indicate (green LED) if the pressure is between the setpoints, mode
„mid-range“ has to be selected. (The measure value is normally between the
setpoints). This mode is only for 2-stage devices available (InBin-P...-2).
In the second step the switching characteristic of the output relay has to be selected:
- „normally closed“ (nc): if the measure value is in the normal range (see above), the
corresponding relays were closed.
- „normally open“ (no): if the measure value is in the normal range (see above), the
corresponding relays were open.
You'll find a detailed desciption of all possible settings in the following section.
Using the menu 1 „Preset“
To beware complexity during the parametrisation process, the InBin-P has several predefined
setups which distinguish between its intended application.
You'll find a detailed desciption of all possible presets in the following section.
Fan speed monitoring
The preset „FAN“ is designed for use in fan speed monitoring applications.
state
output
switch 1
normal
state
output
switch 2
(optional)
setpoint 1
normal
green
green
red
red
setpoint 2
The user has not to set the menu 5 „hysteresis“ and menu 6 „mode“, this will be done via
software. These menus will be skipped during the further parametrisation process.
If the „FAN“-preset has been selected in menu 1, all settings were made as the
following ones:
ventilator
air flow
Menu1: Select "FAN" and press the
enter button.
Filter monitoring
The preset „FILT“ is designed for use in filter monitoring applications.
The user has not to set the menu 5 „hysteresis“ and menu 6 „mode“, this will be done via
software. These menus will be skipped during the further parametrisation process.
If the „FILT“-preset has been selected in menu 1, all settings were made as the following
ones:
Filter
Air flow
Menu1: Select „FILT“ and press the
enter button.
state
output
switch 1
normal
state
output
switch 2
(optional)
setpoint 1
normal
green
green
red
red
setpoint 2
Professional mode
For all other applications the professional mode is designed for.
If the „PRO“-preset has been selected in menu 1, the parametrisation procedure will be
added by two further menus: menu 5 „hysteresis“ and menu 6 „mode“. For this preset the
user has to select the values for the hysteresis and for the mode.
Menu1: Select „PRO“ and press the
enter button.
InBin-P-100
D.IB-P100-02.01-en
23-Aug-2012