E X P L O S I O N P R O O F

5 / 6

no function – menu skip

Using the menu 6 „mode“

Switching characteristic „up-range“ – „normally closed“

state

output

switch 1

normal

state

output

switch 2

(optional)

setpoint 1

normal

green

green

red

red

setpoint 2

„Up-range“: the normal range is above setpoint 1 and setpoint 2

First of all the user has to define the device normal range. For example: 
-  The device should indicate (green LED) if the pressure is under the setpoints, mode 

„down-range“ has to be selected. With other words: the measure value is normally 
under the setpoints.

-  The device should indicate (green LED) if the pressure is over the setpoints, mode

„up-range“ has to be selected. (The measure value is normally over the setpoints.)

-  The device should indicate (green LED) if the pressure is between the setpoints, mode 

„mid-range“ has to be selected. (The measure value is normally between the 
setpoints). This mode is only for 2-stage devices available (InBin-P...-2). 

In the second step the switching characteristic of the output relay has to be selected:
-  „normally closed“ (nc): if the measure value is in the normal range (see above), the 

corresponding relays were closed.   

-  „normally open“ (no): if the measure value is in the normal range (see above), the 

corresponding relays were open.

You'll find a detailed desciption of all possible settings in the following section. 

Using the menu 1 „Preset“

To beware complexity during the parametrisation process, the InBin-P has several predefined 

setups which distinguish between its intended application. 

You'll find a detailed desciption of all possible presets in the following section.  

Fan speed monitoring

The preset „FAN“ is designed for use in fan speed monitoring applications. 

state

output

switch 1

normal

state

output

switch 2

(optional)

setpoint 1

normal

green

green

red

red

setpoint 2

The user has not to set the menu 5 „hysteresis“ and menu 6 „mode“, this will be done via 

software. These menus will be skipped during the further parametrisation process. 

If the „FAN“-preset has been selected in menu 1, all settings were made as the 

following ones:

ventilator

air flow

Menu1: Select "FAN" and press the 
enter button. 

Filter monitoring

The preset „FILT“ is designed for use in filter monitoring applications. 

The user has not to set the menu 5 „hysteresis“ and menu 6 „mode“, this will be done via 

software. These menus will be skipped during the further parametrisation process.

If the „FILT“-preset has been selected in menu 1, all settings were made as the following 

ones:

Filter

Air flow

Menu1: Select „FILT“ and press the 
enter button. 

state

output

switch 1

normal

state

output

switch 2

(optional)

setpoint 1

normal

green

green

red

red

setpoint 2

Professional mode

For all other applications the professional mode is designed for.   

If the „PRO“-preset has been selected in menu 1, the parametrisation procedure will be 

added by two further menus: menu 5 „hysteresis“ and menu 6 „mode“. For this preset the 

user has to select the values for the hysteresis and for the mode.    

Menu1: Select „PRO“ and press the 
enter button. 

InBin-P-100

D.IB-P100-02.01-en

23-Aug-2012

Summary of Contents for InBin-P-100

Page 1: ...connection and cable glands nickel plated screws in stainless steel InBin P 100 OCT as above offshore version seawater resistant with aluminium housing and Amercoat painting stainless steel tubes for clamping ring connection cable glands M20 1 5 mm nickel plated screws in stainless steel Electrical binary pressure or differential pressure switches with adjustable switch activation delay 24 VAC DC ...

Page 2: ...uttons for configuration Housing protection IP66 in acc to IEC 60529 Housing material Aluminium casting coated CT OCT version in Amercoat marine painting seawater resistant OCT Offshore version Dimension weight L W H 180 107 66 mm 950 g Ambient temperature humidity 20 50 C 0 95 rH non condensed Storage temperature 40 70 C Measuring range 0 100 Pa Range scalable on site Minimum measuring range is 5...

Page 3: ...ration A Installation commissioning maintenance The cable has to be drawn through the cable gland After electrical connection the cable gland must be fixed tighten IP66 must be fulfilled In acc with operation InBin switches are maintenance free The sensors must not be opened by the customer For electrical connection use the internal junction box Attention Before opening the internal junction box c...

Page 4: ...steresis select physical unit adjust hysteresis Pa mBar InH2O Menu 6 mode select switching charateristic norm open no norm closed nc Menu 7 Menu 8 Menu 9 Menu 10 Menu 11 Menu 12 Menü 13 Menu 16 Menu 15 lamp select backlight save select save data security select password adjust set 1 select normal sensor interval no yes return default setting on off enter password Menu 14 Menu 1 Preset select appli...

Page 5: ...set To beware complexity during the parametrisation process the InBin P has several predefined setups which distinguish between its intended application You ll find a detailed desciption of all possible presets in the following section Fan speed monitoring The preset FAN is designed for use in fan speed monitoring applications state output switch 1 normal state output switch 2 optional setpoint 1 ...

Page 6: ...t 2 Mid range the normal range is between setpoint 1 and setpoint 2 for 2 stage devices only Switching characteristic mid range normally open state output switch 1 normal state output switch 2 optional setpoint 1 normal green green red red setpoint 2 Mid range the normal range is between setpoint 1 and setpoint 2 for 2 stage devices only Switching characteristic down range normally closed state ou...