Schischek ExReg-V CT Series Manual Download Page 3

E X P L O S I O N P R O O F

PA

PA

PA

5

5

5

6

6

6

7

7

7

8

8

8

10

10

10

9

9

1

1

1

11

11

2

2

2

12

12

13

13

3

3

3

4

4

4

PE

PE

PE

24 VAC/DC

24 VAC/DC

24 VAC/DC

+

~

+

~

+

~

~

~

~

ExReg-V300 

SB 1.0

ExReg-V300-B 

SB 1.2

ExReg-V300-A 

SB 1.1

www.schischek.com

Schischek GmbH Germany, Mühlsteig 45, Gewerbegebiet Süd 5, 90579 Langenzenn, Tel. +49 9101 9081-0, Fax +49 9101 9081-77, E-Mail [email protected]

ExReg-V_en

V02 – 23-Sep-2016

ExReg-V... 
Special options 

...-CT 

...-OCT  ...-VA 

...-OVA

The controller requires a 24 VAC/DC power supply on terminal 1(−/~) and 2 (+/~). Terminals 

1 and 2 are internally connected to terminals 4 and 5 and supplies the control actuator. 

(Note the actuator needs to initialize about 2 A starting current for max. 1 s). The actuator 

is connected directly to the controller over terminals 4–8. If there is less than 1 meter 

The ExReg-V300 is the basic version and can be used for the control of constant volumetric 

flow rates (CAV) and variable flow rates of (VAV). The alarm contact (terminal 3) is used 

as a feedback for normal operation, an analog feedback signal is not provided for these 

devices.

The setpoint is adjusted via terminal 9. The voltage range for the minimum and maximum 

flow rate is defined by a 2...10 V signal. A voltage value of about 12 V opens the damper 

below 0.2 V the damper closes completely. During these forced control functions (damper 

open / close) the controller is without function.

The CAV mode is configured in menu 2 by setting “CAV”. The CAV mode is activated 

when the input voltage is not connected to terminal 9. In this case, the menu 7.2 “default” 

set value is used as a flow. The force control functions (damper open / close) can be 

applied by 0 V (close) and +24 V (open) to terminal 9. This can be done by connecting 

the supply voltage level 0 V and 24 V with two relays.

The simple VAV operation in menu 2 configured via the setting “VAV”. This configuration 

allows a modulation operation in a 2...10 V signal range. In the case of 2 V it is regulated  

on the minimum value set in menu 5 “flow rate” and at 10 V to the maximum value. The 

intermediate values   are according to the voltage level (2...10 V) linearly as setpoints 

available.

ExReg-V300-A is the standard version for the control of variable volume flow (VAV). The 

alarm contact (terminal 3) is used as feedback for normal operation and, in addition, the 

device has an analog output (terminal 11), which outputs the actual value as a continuous 

signal, and an analog feedback of the actuator position (terminal 9). This feature is primarily 

used for energy efficiency.

The setpoint is adjusted via terminal 13. The voltage range for the minimum and maximum 

flow rate is defined as either of 0...10 V or 2...10 V. 

In addition, the positive control function can be used depending on the setting in menu 

6 “set point”. When the voltage value of about 12 V is exceeded the damper opens, when 

it drops below 0.2 V the damper is completely closed. When utilising these force control 

(damper open / close) the controller is without function. If the input is not connected, the 

flow control defaults to the set value in menu 7.2.

AK: Alarm 

contact

Yi: Setpoint actuator 4...20 mA

Ga: Ground 

Y, GND

Uu: actual value actuator 0...10 V

Bus A1 Bus A2 Bus B1 Bus B2

24 V

AC/DC: Supply actuator

AK: Alarm 

contact

Y

i

: Setpoint actuator 4...20 mA

Ga: Ground 

Y, GND

U

U

: actual value actuator 0..10 V

U

U

: Feedback actuator 0...10 V

Ga: Ground

 Y, GND

U

i

: actual value controller 

0/2...10 V

Gr: Ground controller

U

S

: Setpoint controller 
           

0/2...10 V

24 V

AC/DC: Supply actuator

Actuator

AK: Alarm 

contact

Yi: Setpoint actuator 4...20 mA

Ga: Ground 

Y, GND

Uu: actual value actuator 0...10 V

U

S

: Setpoint controller 

0/2...10 V

Ga: Ground

 Y, GND

24 V

AC/DC: Supply actuator

Actuator

Actuator

Galvanic Isolation 1,5 kV

Galvanic Isolation 1,5 kV

Galvanic Isolation 1,5 kV

Bus-Topologie

▪ There must be connected to a bus only point-to-point connections

▪ Star wiring is not permitted

▪ Each device works automatically as a repeater

Electrical Connection

distance between the controller and the actuator, the actuator may be connected directly 

without the use of an additional terminal box. Otherwise please order terminal box (see ac-

cessories).

Attention: Before opening the terminal box cover, the supply voltage must be shut off!

3 / 8

Summary of Contents for ExReg-V CT Series

Page 1: ...dust for use in zone 1 2 21 and 22 Power supply 24 VAC DC Sensor and controller in one housing Direct connection of actuator to the controller s integrated Ex e terminal box No addional Ex i module in panel required No intrinsically safe wiring installation between sensor and panel required No intrinsically safe wiring installation and no space in the panel required Relay output with adjustable al...

Page 2: ...ing 180 107 66 mm stainless steel housing 195 127 70 mm each without connectors Weight 950 g aluminium housing stainless steel version 2 5 kg Ambient temperature 20 50 C storage temperature 35 70 C Ambient humidity 0 95 rH non condensing Sensor circuit Internal intrinsically safe circuit Sensor Piezo pressure transmitter Pressure connection P P sleeves Ø 4 6 mm OCT and OVA versions have 2 stainles...

Page 3: ...n for the control of variable volume flow VAV The alarm contact terminal 3 is used as feedback for normal operation and in addition the device has an analog output terminal 11 which outputs the actual value as a continuous signal and an analog feedback of the actuator position terminal 9 This feature is primarily used for energy efficiency The setpoint is adjusted via terminal 13 The voltage range...

Page 4: ...ation and operation Installation Hazardous area Zone 1 2 21 22 Safe area Control configuration Control speed ExMax CY see additional data sheet Reg V300 and V300 A are designed for the control of volume flows The control mode can be set in menu 8 Controller Normally the fully automatic determination of the control parameters select Auto is sufficient In addition an adaptive PID proportional compon...

Page 5: ... volume Menu 6 Actual value Configuration menu for actual value 6 1 Range Select output value 6 2 Status Indication actual value in m h 1 Language English 2 Application VAV Device ll be recon figurated Continue 3 Sensor Filter 3 1 Filter 20 s Start 0 point compensation 3 3 Status 87 Pa 4 Antrieb Invers 4 1 Invers off 4 2 Test 20 4 3 Status 20 5 Air volume k factor 5 2 k factor 50 5 3 Vnom 1000 m h...

Page 6: ...s 11 1 Input 1 Indication of status terminal 8 11 2 Input 2 Indication of status terminal 9 11 3 Input 3 Indication of status terminal 13 11 4 Output 1 Test output value terminal 6 11 5 Output 2 Test output value terminal 11 7 Nominal value 7 1 Range 0 10 V 7 2 Value 500 m h 7 3 Status 100 m h 8 Controller 8 1 Type Auto 8 2 Gain 100 8 3 P ratio 10 8 4 I ratio 2 0 s 8 5 D ratio 1 0 s 8 6 Tolerance ...

Page 7: ...e parameter 14 2 Use Edit parameter 14 3 Activate Define active parameter 14 4 Erase Delete parameter Menu 15 Leave menu Leave menu and save 11 6 Switch Function open 12 Password 12 1 Level1 0000 12 2 Level 2 0000 12 3 Level 3 0000 13 Indication 13 1 Display on lighted 13 2 Contrast 60 0 13 3 Brightness 100 13 4 Short menu off 14 Parameter 14 1 Save P1 active 14 2 Use P1 active 14 3 Activate P1 oc...

Page 8: ...107 55 66 180 Ø 4 5 Ø 4 5 Ø 4 5 170 213 Reg V OVA www schischek com Schischek GmbH Germany Mühlsteig 45 Gewerbegebiet Süd 5 90579 Langenzenn Tel 49 9101 9081 0 Fax 49 9101 9081 77 E Mail info de schischek com ExReg V_en V02 23 Sep 2016 ExReg V Special options CT OCT VA OVA Dimensions mm Aluminium housing Stainless steel housing 8 8 ...

Reviews: