Schischek ExReg-V CT Series Manual Download Page 2

E X P L O S I O N P R O O F

www.schischek.com

Schischek GmbH Germany, Mühlsteig 45, Gewerbegebiet Süd 5, 90579 Langenzenn, Tel. +49 9101 9081-0, Fax +49 9101 9081-77, E-Mail [email protected]

ExReg-V_en

V02 – 23-Sep-2016

ExReg-V... 
Special options 

...-CT 

...-OCT  ...-VA 

...-OVA

Technical data 

Approbations

Special solutions and accessories

...-CT 

Types in aluminium housing with seawater resistant coating, 

 

parts nickel-plated

...-OCT 

Offshore version in aluminium housing with seawater resistant coating, 

 

parts nickel-plated

...-VA 

Types in stainless steel housing, parts nickel-plated

...-OVA 

Offshore version in stainless steel housing, parts nickel-plated

ExMax-...-CY  Control actuator, 4...20 mA Input, 0...10 V output
ExMax-...-CYF Control actuator, 4...20 mA Input, 0...10 V output with spring return
ExBox-Y/S  Ex-e terminal box, 4 × M20 × 1.5 mm cable glands Ø 6 .. 13 mm
MKR  

Mounting bracket for round ducts up to Ø 600 mm

Kit-S8-CBR  2 cable glands M16 × 1,5 mm, Ex-e, brass nickel-plated, for cable Ø 5...10 mm
Kit 2  

Flexible pressure tube, 2 m, inner Ø 6 mm, 2 connection nipples

Kit-PTC-CBR  2 connecting tubes for tube fittings Ø 6 mm, stainless steel 316 L

Supply voltage / frequency 24 

VAC/DC ± 15 % (20,4...27,6 VAC/DC), frequency 50...60 Hz 

Current, power consumption 

150 mA, ~ 3 W, internal fuse 500 mAT, without bracket, not removable

Galvanic isolation 

Supply for analogue in- and outputs min. 1,5 kV, supply for relay output min. 1,5 kV

Electrical connection  

Terminals 0,14...2,5 mm² at integrated Ex-e terminal box, stripping length 9 mm, torque 0,4…0,5 Nm, equipotential bonding 4 mm²

Cable glands  

2 × M16 × 1,5 mm, Ex-e approved, for cable diameter ~ Ø 4...10 mm 

Cable glands ...-CT  

2 × M16 × 1,5 mm, Ex-e approved, brass nickel-plated, for cable diameter ~ Ø 6...10 mm

                       ...-VA, ...-OCT, ...-OVA  2 × M20 × 1,5 mm, Ex-e approved, brass nickel-plated, for cable diameter ~ Ø 6...13 mm
Protection class  

Class I (grounded)

Display 

 

LCD matrix display with backlight, display for configuration, user guidance, parameter and actual value indication 

Control elements 

 

3 buttons for configuration

Housing material 

Aluminium die-cast housing, coated. Optional with seawater resistant coating (...-CT/...-OCT) or stainless steel housing, 

 

№ 1.4581 / UNS-J92900 / similar AISI 316Nb (...-VA/...-OVA)

Dimensions (L × W × H) 

Aluminium housing ~ 180 × 107 × 66 mm, stainless steel housing ~ 195 × 127 × 70 mm (each without connectors)

Weight 

~ 950 g aluminium housing, stainless steel version ~ 2,5 kg

Ambient temperature 

−20...+50 °C, storage temperature −35...+70 °C

Ambient humidity 

0...95 % rH, non condensing

Sensor circuit 

 

Internal intrinsically safe circuit

Sensor  Piezo pressure transmitter
Pressure connection   

P+ / P− sleeves Ø 4...6 mm. OCT and OVA versions have 2 stainless steel (316L) tube connections for clamp ring fittings Ø 6 mm

Measuring range  

 

0…300 Pa, minimum measuring range is 2 % of full scale 

Sensor damping (filter) 

1...50 seconds, adjustable

Accuracy of pressure  

± 2,5 % full scale ± 1 Pa

Setting zero point   

Via menu. Short-circuit mechanically both tube connectors P+ / P− for the moment of zero point setting

Air flow 

 

Calculation via k-factor (”shield factor”); adjustable parameters: V

 max

, V

 min

, V

 rated

, k-factor

Regulation 

 

Adaptive PID controller (automatic or manual mode selectable)

Control tolerance 

 

1...5 % adjustable

Delay time 

 

3 s

Alarm monitoring    

Monitoring the volume flow; adjustable functions: tolerance limit (fixed and variable value), alarm delay

Alarm contact  

(terminal 3)  Relay; max. values: 0.1 A (30 VAC/DC), min. values: 10 mW / 0.1 V / 1 mA

Life time    mechanically 

10 × 10

6

 

                   electrically (rated) 

100 × 10

3

Current output  

(terminal 6)  Range 4...20 mA, invertible, basic accuracy ± 1.0 % of full scale, load < 500 Ω, influence < 0.1 %, open circuit voltage 24 V

Voltage input  

(terminal 8)  Range 0...10 V,    invertible, basic accuracy ± 1.0 % of full scale, over-voltage up to 30 V 

Voltage input  

(terminal 9)  Range 0...10 V,  adjustable, basic accuracy ± 1.0 % of full scale, over-voltage up to 30 V

Voltage output  

(terminal 11)  Range 0...10 V,  adjustable, basic accuracy ± 1.0 % of full scale, load > 10 kΩ, influence < 0.1 %, short circuit proof (type ...Reg-V300-A)

Voltage input  

(terminal 13)  Range 0...10 V,  adjustable, basic accuracy ± 1.0 % of full scale, over-voltage up to 30 V (type ...Reg-V300-A)

Wiring diagram  

SB 

1.0 / 1.1 / 1.2

Scope of delivery 

Sensor, 3 self-tapping screws 4,2 × 13 mm resp. in stainless steel (with ...CT and ...VA versions), short circuit tube

ATEX directive  

2014/34/EU

EC type-approved  

EPS 11 ATEX 1 380

IECEx certified  

IECEx EPS 12.0028

Approval for gas 

  II 2 (1) G   Ex e mb ib [ia Ga] IIC T6 Gb

  Types ...-CT, ...-OCT  II 2 (1) G   Ex e mb ib [ia Ga] IIB T6 Gb
Approval for dust 

  II 2 (1) D   Ex tb ib [ia Da] IIIC T80°C Db IP66

CE identification   CE 

№ 0158 

EMC directive  

2014/34/EU

Enclosure protection   IP66 in acc. with EN 60529

2 / 8

Summary of Contents for ExReg-V CT Series

Page 1: ...dust for use in zone 1 2 21 and 22 Power supply 24 VAC DC Sensor and controller in one housing Direct connection of actuator to the controller s integrated Ex e terminal box No addional Ex i module in panel required No intrinsically safe wiring installation between sensor and panel required No intrinsically safe wiring installation and no space in the panel required Relay output with adjustable al...

Page 2: ...ing 180 107 66 mm stainless steel housing 195 127 70 mm each without connectors Weight 950 g aluminium housing stainless steel version 2 5 kg Ambient temperature 20 50 C storage temperature 35 70 C Ambient humidity 0 95 rH non condensing Sensor circuit Internal intrinsically safe circuit Sensor Piezo pressure transmitter Pressure connection P P sleeves Ø 4 6 mm OCT and OVA versions have 2 stainles...

Page 3: ...n for the control of variable volume flow VAV The alarm contact terminal 3 is used as feedback for normal operation and in addition the device has an analog output terminal 11 which outputs the actual value as a continuous signal and an analog feedback of the actuator position terminal 9 This feature is primarily used for energy efficiency The setpoint is adjusted via terminal 13 The voltage range...

Page 4: ...ation and operation Installation Hazardous area Zone 1 2 21 22 Safe area Control configuration Control speed ExMax CY see additional data sheet Reg V300 and V300 A are designed for the control of volume flows The control mode can be set in menu 8 Controller Normally the fully automatic determination of the control parameters select Auto is sufficient In addition an adaptive PID proportional compon...

Page 5: ... volume Menu 6 Actual value Configuration menu for actual value 6 1 Range Select output value 6 2 Status Indication actual value in m h 1 Language English 2 Application VAV Device ll be recon figurated Continue 3 Sensor Filter 3 1 Filter 20 s Start 0 point compensation 3 3 Status 87 Pa 4 Antrieb Invers 4 1 Invers off 4 2 Test 20 4 3 Status 20 5 Air volume k factor 5 2 k factor 50 5 3 Vnom 1000 m h...

Page 6: ...s 11 1 Input 1 Indication of status terminal 8 11 2 Input 2 Indication of status terminal 9 11 3 Input 3 Indication of status terminal 13 11 4 Output 1 Test output value terminal 6 11 5 Output 2 Test output value terminal 11 7 Nominal value 7 1 Range 0 10 V 7 2 Value 500 m h 7 3 Status 100 m h 8 Controller 8 1 Type Auto 8 2 Gain 100 8 3 P ratio 10 8 4 I ratio 2 0 s 8 5 D ratio 1 0 s 8 6 Tolerance ...

Page 7: ...e parameter 14 2 Use Edit parameter 14 3 Activate Define active parameter 14 4 Erase Delete parameter Menu 15 Leave menu Leave menu and save 11 6 Switch Function open 12 Password 12 1 Level1 0000 12 2 Level 2 0000 12 3 Level 3 0000 13 Indication 13 1 Display on lighted 13 2 Contrast 60 0 13 3 Brightness 100 13 4 Short menu off 14 Parameter 14 1 Save P1 active 14 2 Use P1 active 14 3 Activate P1 oc...

Page 8: ...107 55 66 180 Ø 4 5 Ø 4 5 Ø 4 5 170 213 Reg V OVA www schischek com Schischek GmbH Germany Mühlsteig 45 Gewerbegebiet Süd 5 90579 Langenzenn Tel 49 9101 9081 0 Fax 49 9101 9081 77 E Mail info de schischek com ExReg V_en V02 23 Sep 2016 ExReg V Special options CT OCT VA OVA Dimensions mm Aluminium housing Stainless steel housing 8 8 ...