Compact. Easy installation. Universal. Cost effective. Safe.

Product views and applications

Description

Highlights

Electrical, explosion-proof volume flow controller (CAV / VAV)

in conjunction with ExMax-...-CY... actuators only

24 VAC/DC supply, adaptive PID controller, alarm contact

EC type-approved in acc. with ATEX directive 2014/34/EU for zone 1, 2, 21, 22

ExReg-V

  Volume flow controller  0...300 Pa

Type 

Sensor 

Supply 

Range  

Connection / Interface (analogue)  

Alarm contact 

Wiring diagram

ExReg- V-300 

Diff. pressure  24 VAC/DC 

0...300 Pa  1 × actuator, 1 × set point 

Relay contact 30 V / 0.1 A 

SB 1.0

ExReg- V-300 - A  Diff. pressure  24 VAC/DC 

0...300 Pa  1 × actuator, 1 × set point, 1 × actual value, 1 × position actuator  Relay contact 30 V / 0.1 A 

SB 1.1

ExReg- V-300 - B  Diff. pressure  24 VAC/DC 

0...300 Pa  1 × actuator, RS485 communication 

Relay contact 30 V / 0.1 A 

SB 1.2

ExReg- V- ...  - CT  Types as above with aluminium housing and seawater resistant coating (cable glands M16 brass nickel-plated, screws in stainless steel)
ExReg- V- ...  - OCT  Types as above, offshore version with aluminium housing and seawater resistant coating (stainless steel tubes for clamping ring connection, 
 

cable glands M20 brass nickel-plated, screws in stainless steel)

ExReg- V- ...  - VA  Types as above with stainless steel housing for aggressive ambient (cable glands M20 brass nickel-plated, screws in stainless steel)
ExReg- V- ...  - OVA  Types as above, offshore version with stainless steel housing for aggressive ambient (tubes for clamping ring connection and screws in stainless steel, 
 

cable glands M20 brass nickel-plated)

► For all type of gas, mists, vapours and dust for use in zone 1, 2, 21 and 22

► Power supply 24 VAC/DC

► Sensor and controller in one housing

► Direct connection of actuator to the controller’s integrated Ex-e terminal box

► No addional Ex-i module in panel required

► No intrinsically safe wiring/installation between sensor and panel required

► No intrinsically safe wiring/installation and no space in the panel required

► Relay output with adjustable alarm monitoring

► Scalable analogue input and output (selectable für setpoint, actual value, et al.)

► Optional analogue output for controller feedback 

► Adjustable  k-factor, universially applicable for any dampers

►Display with backlight, can be switched off

► Password locking 

► Down to −20 °C ambient temperature applicable

► Compact design and small dimension 

► Robust aluminium housing (optional with seawater resistant coating) or in stainless steel

► IP66 protection

► Offshore versions with pressure tube connection for clamping ring Ø 6 mm

The ExReg-V... flow controller is an indispensable integrant in Building 

Management Control Equipment for Chemical, Pharmaceutical, Industrial 

and Offshore plants for use in hazardous areas of zones 1, 2 (gas) and 

21, 22 (dust).

Highest protection class (ATEX) and IP66 protection, small dimensions, 

universal functions and technical data as well as an optional stainless 

steel housing guarantee safe operation even in harsh environments. 

ExReg-V... is used directly in hazardous areas for control of air flows in 

ventilation systems. To complete the technical solution an additional 

damper actuator type ExMax-...-CY or ExMax-...-CYF (with Fail Safe 

spring return) is required and also a ventilation damper with orifice plate 

and a known shield factor (called k-factor).

All controllers are programmable on site with menu guide. The internal 

PID control structure is simple to use and automatically configured for 

standard applications. The display shows the current status during 

operation for the actual value, setpoint and actuator position (can be 

disabled if required).

...Reg-V...-OCT and ...-OVA offshore versions are equipped with stain-

less steel tubing Ø 6 mm. 

ExMax-...-CY...  –  see additional data sheet

 

NICHT freigegeben !

Volume flow controller

1 / 8

Summary of Contents for ExReg-V CT Series

Page 1: ...dust for use in zone 1 2 21 and 22 Power supply 24 VAC DC Sensor and controller in one housing Direct connection of actuator to the controller s integrated Ex e terminal box No addional Ex i module in panel required No intrinsically safe wiring installation between sensor and panel required No intrinsically safe wiring installation and no space in the panel required Relay output with adjustable al...

Page 2: ...ing 180 107 66 mm stainless steel housing 195 127 70 mm each without connectors Weight 950 g aluminium housing stainless steel version 2 5 kg Ambient temperature 20 50 C storage temperature 35 70 C Ambient humidity 0 95 rH non condensing Sensor circuit Internal intrinsically safe circuit Sensor Piezo pressure transmitter Pressure connection P P sleeves Ø 4 6 mm OCT and OVA versions have 2 stainles...

Page 3: ...n for the control of variable volume flow VAV The alarm contact terminal 3 is used as feedback for normal operation and in addition the device has an analog output terminal 11 which outputs the actual value as a continuous signal and an analog feedback of the actuator position terminal 9 This feature is primarily used for energy efficiency The setpoint is adjusted via terminal 13 The voltage range...

Page 4: ...ation and operation Installation Hazardous area Zone 1 2 21 22 Safe area Control configuration Control speed ExMax CY see additional data sheet Reg V300 and V300 A are designed for the control of volume flows The control mode can be set in menu 8 Controller Normally the fully automatic determination of the control parameters select Auto is sufficient In addition an adaptive PID proportional compon...

Page 5: ... volume Menu 6 Actual value Configuration menu for actual value 6 1 Range Select output value 6 2 Status Indication actual value in m h 1 Language English 2 Application VAV Device ll be recon figurated Continue 3 Sensor Filter 3 1 Filter 20 s Start 0 point compensation 3 3 Status 87 Pa 4 Antrieb Invers 4 1 Invers off 4 2 Test 20 4 3 Status 20 5 Air volume k factor 5 2 k factor 50 5 3 Vnom 1000 m h...

Page 6: ...s 11 1 Input 1 Indication of status terminal 8 11 2 Input 2 Indication of status terminal 9 11 3 Input 3 Indication of status terminal 13 11 4 Output 1 Test output value terminal 6 11 5 Output 2 Test output value terminal 11 7 Nominal value 7 1 Range 0 10 V 7 2 Value 500 m h 7 3 Status 100 m h 8 Controller 8 1 Type Auto 8 2 Gain 100 8 3 P ratio 10 8 4 I ratio 2 0 s 8 5 D ratio 1 0 s 8 6 Tolerance ...

Page 7: ...e parameter 14 2 Use Edit parameter 14 3 Activate Define active parameter 14 4 Erase Delete parameter Menu 15 Leave menu Leave menu and save 11 6 Switch Function open 12 Password 12 1 Level1 0000 12 2 Level 2 0000 12 3 Level 3 0000 13 Indication 13 1 Display on lighted 13 2 Contrast 60 0 13 3 Brightness 100 13 4 Short menu off 14 Parameter 14 1 Save P1 active 14 2 Use P1 active 14 3 Activate P1 oc...

Page 8: ...107 55 66 180 Ø 4 5 Ø 4 5 Ø 4 5 170 213 Reg V OVA www schischek com Schischek GmbH Germany Mühlsteig 45 Gewerbegebiet Süd 5 90579 Langenzenn Tel 49 9101 9081 0 Fax 49 9101 9081 77 E Mail info de schischek com ExReg V_en V02 23 Sep 2016 ExReg V Special options CT OCT VA OVA Dimensions mm Aluminium housing Stainless steel housing 8 8 ...

Reviews: