Firmware Design
P746/EN FD/G31
MiCOM P746
(FD) 9-
11
FD
2.3.3
Universal opto isolated logic inputs
The P746 relay is fitted with universal opto isolated logic inputs that can be programmed for
the nominal battery voltage of the circuit of which they are a part. i.e. thereby allowing
different voltages for different circuits e.g. signalling, tripping. They nominally provide a Logic
1 or "ON" value for Voltages 80% of the set voltage and a Logic 0 or "OFF" value for the
voltages 60% of the set voltage. This lower value eliminates fleeting pickups that may occur
during a battery earth fault, when stray capacitance may present up to 50% of battery
voltage across an input. Each input has filtering of 7ms. This renders the input immune to
induced noise on the wiring: although this method is secure it can be slow.
In the Opto Config. menu the nominal battery voltage can be selected for all opto inputs by
selecting one of the five standard ratings in the Global Nominal V settings. If Custom is
selected then each opto input can individually be set to a nominal voltage value.
Setting Range
Menu Text
Default Setting
Min.
Max.
Step Size
OPTO CONFIG
Global Nominal V
48/54V
24/27V, 30/34V, 48/54V, 110/125V,
220/250V, Custom
Opto Input x
48/54V
24/27V, 30/34V, 48/54V, 110/125V,
220/250V
2.4
Power supply module (including output relays)
The power supply module contains two PCBs, one for the power supply unit itself and the
other for the output relays. The power supply board also contains the input and output
hardware for the rear communication port which provides an EIA(RS)485 communication
interface.
2.5
Power supply board (including EIA(RS)485 communication interface)
One of three different configurations of the power supply board can be fitted to the relay.
This will be specified at the time of order and depends on the nature of the supply voltage
that will be connected to the relay. The three options are shown in table 1 below:
Nominal dc Range
Nominal ac Range
24/54 V
DC only
48/125 V
30/100 Vrms
110/250 V
100/240 Vrms
Table 1:
Power supply options
The outputs from all versions of the power supply module are used to provide isolated power
supply rails to all of the other modules within the relay. Three voltage levels are used within
the relay, 5.1V for all of the digital circuits, 16V for the analogue electronics, e.g. on the
input board, and 22V for driving the output relay coils and communication boards 3.3V power
supply (through on board DC-DC converter).
All power supply voltages including the 0V ground line are distributed around the relay via
the 64-way ribbon cables. One further voltage level is provided by the power supply board
which is the field voltage of 48V. This is brought out to terminals on the back of the relay so
that it can be used to drive the optically isolated digital inputs.
The two other functions provided by the power supply board are the RS485 communications
interface and the watchdog contacts for the relay. The RS485 interface is used with the
relay’s rear communication port to provide communication using K Bus Courier. The RS485
hardware supports half-duplex communication and provides optical isolation of the serial
data being transmitted and received.
All internal communication of data from the power supply board is conducted via the output
relay board which is connected to the parallel bus.
Summary of Contents for MiCOM P746
Page 4: ......
Page 5: ...Pxxx EN SS G11 SAFETY SECTION...
Page 6: ......
Page 8: ...Pxxx EN SS G11 Page 2 8 Safety Section BLANK PAGE...
Page 16: ...P746 EN IT G31 Introduction MiCOM P746...
Page 18: ...P746 EN IT G31 Introduction IT 1 2 MiCOM P746 IT BLANK PAGE...
Page 26: ...P746 EN TD G31 Technical Data MiCOM P746...
Page 38: ...P746 EN GS G31 Getting Started MiCOM P746...
Page 78: ...P746 EN ST G31 Getting Started MiCOM P746...
Page 80: ...P746 EN ST G31 Settings ST 4 2 MiCOM P746 ST BLANK PAGE...
Page 112: ...P746 EN ST G31 Settings ST 4 34 MiCOM P746 ST BLANK PAGE...
Page 114: ...P746 EN OP G31 Operation MiCOM P746...
Page 136: ...P746 EN OP G31 Operation OP 5 22 MiCOM P746 OP BLANK PAGE...
Page 138: ...P746 EN AP G31 Application Notes MiCOM P746...
Page 142: ...P746 EN AP G31 Application Notes AP 6 4 MiCOM P746 AP BLANK PAGE...
Page 194: ...P746 EN AP G31 Application Notes AP 6 56 MiCOM P746 AP BLANK PAGE...
Page 196: ...P746 EN PL G31 Programmable Logic MiCOM P746...
Page 238: ...P746 EN MR A11 Measurements and Recording MiCOM P746...
Page 240: ...P746 EN MR A11 Measurements and Recording MR 8 2 MiCOM P746 MR BLANK PAGE...
Page 258: ...P746 EN FD G31 Firmware Design MiCOM P746...
Page 280: ......
Page 348: ...P746 EN MT A11 Maintenance MiCOM P746...
Page 350: ...P746 EN MT A11 Maintenance MT 11 2 MiCOM P746 MT BLANK PAGE...
Page 364: ...P746 EN MT A11 Maintenance MT 11 16 MiCOM P746 MT BLANK PAGE...
Page 366: ...P746 EN TS G31 Troubleshooting MiCOM P746...
Page 368: ...P746 EN TS G31 Troubleshooting TS 12 2 MiCOM P746 TS BLANK PAGE...
Page 382: ...P746 EN SC G31 SCADA Communications MiCOM P746...
Page 424: ...P746 EN SC G31 SCADA Communications SC 13 42 MiCOM P746 SC BLANK PAGE...
Page 426: ...P746 EN SG F21 Symbols and Glossary MiCOM P746...
Page 438: ......
Page 440: ...P746 EN IN G31 Installation IN 15 2 MiCOM P746 IN BLANK PAGE...
Page 468: ......
Page 470: ...P746 EN HI G31 Remote HMI HI 16 2 MiCOM P746 HI BLANK PAGE...
Page 500: ...P746 EN HI G31 Remote HMI HI 16 32 MiCOM P746 HI BLANK PAGE...
Page 502: ......
Page 504: ...P746 EN CS A11G31 Cyber Security CS 17 2 MiCOM P746 CS BLANK PAGE...
Page 524: ...P746 EN VH G31 Firmware and Service Manual Version History MiCOM P746...
Page 529: ......