Application Notes
P746/EN AP/G31
MiCOM P746
(AP) 6-
13
AP
Explanations of the values:
1.
ID>1 shall be higher than 120% of the highest phase to neutral fault to not operate in
case of phase to neutral fault.
2.
Slope k1 recommendation is 10% to meet 10Pxx current transformers
3.
Slope k2 (ID>2) recommendation is 50 / 65%
To be always stable in the worth CT ratio conditions (between the biggest CT and the
smallest CT). 60% is OK as long as the CT ratio is less than 5.
1.
ID>2 shall be lower than 80% of the minimum phase to phase fault current to operate
sub-cycle for the minimum fault and higher than 120% Iload Max (120% to allow 20%
margin) and if possible equal to 6 × (ID>1) to be insensitive to the worth CT saturation.
2.
IDCZ>2 same as ID>2
3.
Slope kCZ (IDCZ>2) recommendation is 30%
The requirement is to be able to trip for a fault that is counted twice by the Check Zone (for
example one and half circuit breaker substation).
2.3
Additional protection settings
2.3.1
Dead Zone protection (DZ)
On a feeder, if the isolators or the breaker is open, a dead zone (or end zone) is said to exist
between the open element and the CT. The P746 can protect this zone with the Dead Zone
protection. This is a simple time delayed overcurrent element which is only active when a
dead zone is identified in the local topology.
2.3.1.1 Setting
guidelines
For each CT connected to a Feeder Circuit Breaker (not on bus couplers or bus sections)
For the phase:
•
I>DZ must be below 80% of the minimum Dead Zone fault level (and if possible bigger
than the maximum load).
•
I>DZ Time delay must be at least 50ms if the CB status positions are used (any value
otherwise)
IMPORTANT NOTE:
When a dead zone fault occurs and the bias current flowing through the bus is small,
there could be a maloperation of the 87BB.
To prevent that, it is recommended to enable an additional criterion such as voltage
(voltage criteria can be used for single busbar only in one box mode).
2.3.2
Circuit Breaker Fail (CBF)
2.3.2.1 Setting
guidelines
Typical timer settings to use are as follows:
CB fail reset mechanism tBF time delay
Typical delay for 2 cycle
circuit breaker
CB open
CB auxiliary contacts
opening/ closing time (max.) +
error in tBF timer + safety margin
50 + 10 + 50 = 110 ms
Undercurrent elements
CB interrupting time +
undercurrent element (max.) +
safety margin operating time
50 + 15 + 20 = 85 ms
Summary of Contents for MiCOM P746
Page 4: ......
Page 5: ...Pxxx EN SS G11 SAFETY SECTION...
Page 6: ......
Page 8: ...Pxxx EN SS G11 Page 2 8 Safety Section BLANK PAGE...
Page 16: ...P746 EN IT G31 Introduction MiCOM P746...
Page 18: ...P746 EN IT G31 Introduction IT 1 2 MiCOM P746 IT BLANK PAGE...
Page 26: ...P746 EN TD G31 Technical Data MiCOM P746...
Page 38: ...P746 EN GS G31 Getting Started MiCOM P746...
Page 78: ...P746 EN ST G31 Getting Started MiCOM P746...
Page 80: ...P746 EN ST G31 Settings ST 4 2 MiCOM P746 ST BLANK PAGE...
Page 112: ...P746 EN ST G31 Settings ST 4 34 MiCOM P746 ST BLANK PAGE...
Page 114: ...P746 EN OP G31 Operation MiCOM P746...
Page 136: ...P746 EN OP G31 Operation OP 5 22 MiCOM P746 OP BLANK PAGE...
Page 138: ...P746 EN AP G31 Application Notes MiCOM P746...
Page 142: ...P746 EN AP G31 Application Notes AP 6 4 MiCOM P746 AP BLANK PAGE...
Page 194: ...P746 EN AP G31 Application Notes AP 6 56 MiCOM P746 AP BLANK PAGE...
Page 196: ...P746 EN PL G31 Programmable Logic MiCOM P746...
Page 238: ...P746 EN MR A11 Measurements and Recording MiCOM P746...
Page 240: ...P746 EN MR A11 Measurements and Recording MR 8 2 MiCOM P746 MR BLANK PAGE...
Page 258: ...P746 EN FD G31 Firmware Design MiCOM P746...
Page 280: ......
Page 348: ...P746 EN MT A11 Maintenance MiCOM P746...
Page 350: ...P746 EN MT A11 Maintenance MT 11 2 MiCOM P746 MT BLANK PAGE...
Page 364: ...P746 EN MT A11 Maintenance MT 11 16 MiCOM P746 MT BLANK PAGE...
Page 366: ...P746 EN TS G31 Troubleshooting MiCOM P746...
Page 368: ...P746 EN TS G31 Troubleshooting TS 12 2 MiCOM P746 TS BLANK PAGE...
Page 382: ...P746 EN SC G31 SCADA Communications MiCOM P746...
Page 424: ...P746 EN SC G31 SCADA Communications SC 13 42 MiCOM P746 SC BLANK PAGE...
Page 426: ...P746 EN SG F21 Symbols and Glossary MiCOM P746...
Page 438: ......
Page 440: ...P746 EN IN G31 Installation IN 15 2 MiCOM P746 IN BLANK PAGE...
Page 468: ......
Page 470: ...P746 EN HI G31 Remote HMI HI 16 2 MiCOM P746 HI BLANK PAGE...
Page 500: ...P746 EN HI G31 Remote HMI HI 16 32 MiCOM P746 HI BLANK PAGE...
Page 502: ......
Page 504: ...P746 EN CS A11G31 Cyber Security CS 17 2 MiCOM P746 CS BLANK PAGE...
Page 524: ...P746 EN VH G31 Firmware and Service Manual Version History MiCOM P746...
Page 529: ......